2 : ALL (Stdstl)<br />

Chapter 8 Applied Functions<br />

Motor parameter is measured when motor is stopped. Measure stator resistance(Rs), leak inductance(Lsigma), and the<br />

rotor time constant(Tr) all together at the same time. This mode is available when Control Mode(DRV-09) is Sensorless-2.<br />

3 : Rs+Lsigma<br />

The parameter is measured with the motor not operating. The measured values are used for auto torque boost and<br />

sensorless vector control. Because the motor is not rotating, the connection between the motor axis and load does not<br />

affect the parameter measurement. However, be careful not to rotate the motor axis at the load side.<br />

4 : Enc. Test<br />

Connect the encoder option card to the main body of the inverter and connect the encoder cable attached to the motor to<br />

the option card. The motor checks connection and misconnection of A and B pulses. Be sure to set related functions<br />

correctly for encoder state measurement.<br />

5 : Tr<br />

When Control Mode(DRV-09) is Vector, the motor measures the rotor time constant(Tr) while rotating. If Control<br />

Mode(DRV-09) is Sensorless-2, the motor measures the rotor time constant(Tr) while static.<br />

If Control Mode(DRV-09) shifts from Sensorless2 to Vector, you should conduct time constant(Tr) tuning again.<br />

BAS-21 Rs ~ BAS-24 Tr, BAS-14 Noload Curr : Displays the motor parameter measured in auto tuning. Of the auto tuning<br />

selected above, for the parameter missing from the measurement items, the default value is displayed.<br />

2) Encoder Connection Status Measurement<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

BAS 20 Auto Tuning 3 Enc Test 0~4 -<br />

01 Enc Opt Mode 1 Feed-back 0~2 -<br />

04 Enc Type Sel 0 Line <strong>Drive</strong>r 0~2 -<br />

APO 05 Enc Pulse Sel 0 (A+B) 0~2 -<br />

06 Enc Pulse Num - 1024 10~4096 -<br />

08 Enc Monitor - 0 - -<br />

APO-01 Enc Opt Mode : Set at No. 1 Feed-back.<br />

APO-04 Enc Type Sel : Selects the encoder signal transmission method according to the encoder manual. One of Line<br />

<strong>Drive</strong>r(0), Totem or Com(1) and Open Collect(2) is selected.<br />

8-19