Chapter 10 Protective Functions<br />

10-9<br />

External Trip A contact point<br />

External Trip B contact point<br />

10.1.7 <strong>Inverter</strong> overload<br />

If more current than the rated inverter current flows, the protective function starts to protect the inverter according to the inverse<br />

time characteristic.<br />

Group Code No. Function Display Setting Display Unit<br />

OUT 31~33 Relay 1,2, Q1 6 IOL -<br />

Warning signals can be produced in advance by using the multi-function output terminal before the inverter overload<br />

protective function(IOLT) starts. The warning signal is released when 60% of the inverter overload protective<br />

action(150%, 1 minute) lapses.<br />

10.1.8 Keypad command loss<br />

If a problem occurs with the communication during operation or the connection between the keypad and the main body with the<br />

operating command method being keypad, the inverter action is selected.<br />

Group Code No. Function Display Setting Display Unit<br />

PRT 11 Lost KPD Mode 2 Free-Run -<br />

OUT 31~33 Relay1,2, Q1 30 Lost Keypad -<br />

DRV 06 Cmd Source 0 Keypad -<br />

CNF 22 Multi Key Sel 0 JOG Key -<br />

PRT-11 Lost KPD Mode : Set the operating command(DRV-06) at No. 0 keypad, No. 2 Free-Run or No. 3 DEC. In<br />

case of a problem with the communication between the keypad and main body, the output is blocked or the inverter<br />

conducts a decelerating stop according to the set method. Set at No. 0 None, it does nothing in case of keypad<br />

command loss. Set at No. 1 Warning, a warning signal is released in case of a failure if No. 29 Lost Keypad, of the<br />

multi-function output or relay functions, is selected. In case of decelerating stop, the deceleration occurs for the time set<br />

at PRT-07 Trip Dec Time. The protective action is also available for the keypad command loss during jog key operation<br />

when CNF-22 is set as JOG Key.<br />

Frequency<br />

P7(A contact point)<br />

P8(B contact point)<br />

Operating<br />

command