7.1.8 Run immediately with power On: Power-on Run<br />

Chapter 7 Basic Functions<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

DRV 06 Cmd Source - 1 ~ 2 - -<br />

ADV 10 Power-on Run 1 --- yes --- No/Yes -<br />

With power supplied to the inverter and the terminal block operating command being ON, the inverter starts operating.<br />

This is effective only when the DRV Group 06 command source is set at 1 (Fx/Rx-1) or 2 (Fx/Rx-2). At this time, if load<br />

(Fan load) is on the status of Free-Run, Trip may be occurred while operating. Change the bit 4 to 1 at CON-71 Speed<br />

Search and it makes the inverter can start with Speed Search. If not, inverter will be accelerating normal V/F pattern<br />

without Speed Search.<br />

If this function is not selected, operation resumes after the operating commands is turned OFF and ON again.<br />

Caution<br />

Be careful with this function, which causes the motor to rotate as soon as the power is<br />

supplied.<br />

7.1.9 Restarts by reset after trip: RST Restart<br />

Group Code No. Function Display Setting Display default Setting Range Unit<br />

DRV 06 Cmd Source - FX/RX-1<br />

or FX/RX-2<br />

FX/RX-1 1~2 -<br />

08 RST Restart 1 -- yes -- 0:No No(1)/Yes(1) -<br />

PRT 09 Retry Number 1 0 0~10 -<br />

10 Retry Delay 1.0 1.0 0~60.0 sec<br />

The inverter resumes if the terminal block operating command is ON when it is reset after a trip. <strong>Inverter</strong> cut the output<br />

when inverter trip is occurred and motor run to Free-Run. At this time, inverter trip can be occurred. Change the bit 2<br />

to 1 at CON-71 Speed Search and <strong>Inverter</strong> will be start with Speed Search when trip is released. If not, inverter will be<br />

accelerating normal V/F pattern without Speed Search.<br />

If this function is not used, operation resumes when the operating command is turned OFF and then ON again after<br />

resetting.<br />

Power<br />

Frequency<br />

Operating<br />

command<br />

When ADV-10=0 When ADV-10=1<br />

7-15