Chapter 9 Monitor Functions<br />

9.1.4 Selection of relay function and multi-function output terminal of terminal block<br />

9-10<br />

Group Code No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

30 Trip Out Mode - 010 bit<br />

OUT<br />

31 Relay 1 Trip Mode -<br />

32 Relay 2 12 Run -<br />

33 Q1 Define 1 FDT-1<br />

34~36 Q2~Q4 Define - - -<br />

41 DO Status - - bit<br />

According to OUT-30 Failure output, Failure Relay will operate<br />

Bit on status (ON) : Bit off status (OFF) :<br />

Setting option Function<br />

Bit3 Bit2 Bit1 Right end of the window is ‘ Bit 1’<br />

� It operates, when the Low voltage trip occurs<br />

� It operates under trip situations other than low voltage trip.<br />

�<br />

It operates under the final failure of automatic restart<br />

repetition setting trials. (PRT-08~09).<br />

Select the output items of the multi-function output terminal(Q1) and relay(Relay1, 2) of the inverter terminal block.<br />

Q1 is Open Collector TR output.<br />

Extended I/O card mounted in the inverter body, you can use additional 3 relay outputs and function codes OUT-34,<br />

35 and 36 are displayed.<br />

Multi-function output can be monitored at OUT 41 DO Status.<br />

Multi-function output can be monitored to 3 outputs without extended I/O and 6 outputs with extended I/O.<br />

1) Multi-Function output Terminal & Relay setting Functions<br />

0: None (I recommend it is more easily described)<br />

It takes no action. If this multi-function output is set as None with the PLC option card inserted in Slot 1 and Slot 2, it<br />

can be used as the contact point output of the PLC option card.<br />

1: FDT-1<br />

This inspects whether the output frequency of the inverter has reached the frequency set by the user. It begins to<br />

operate when the following condition is met.<br />

absolute value(set frequency – output frequency) < detected frequency width/2