Chapter 9 Monitor Functions<br />

9-8<br />

Setting Function<br />

10<br />

11<br />

12<br />

13<br />

14<br />

Speed<br />

Fdb<br />

Speed<br />

Dev<br />

PID Ref<br />

Value<br />

PID Fdb<br />

Value<br />

PID<br />

Output<br />

Displays the information on the speed of the input into the<br />

encoder option card. It produces 10V at maximum<br />

frequency(DRV-20)<br />

Outputs the difference between the speed<br />

reference(command) and the motor’s rotation speed that<br />

inputs into the encoder option card. It produces 10V at twice<br />

the rated slip frequency. It is valid only in the vector control<br />

mode.<br />

Outputs the command values of the PID controller. It<br />

produces 6.6V at 100% of the reference.<br />

Displays the amount of the feedback of the PID controller. It<br />

produces 6.6V at 100% of the reference.<br />

Displays the output value of the PID controller. It produces<br />

6.6V at 100% of the reference.<br />

15 Constant Outputs the value of OUT-05 AO1 Const %.<br />

OUT-02 AO1 Gain, OUT-03 AO1 Bias : The size and offset can be adjusted. The output items are selected as<br />

frequency and the operation is as follows.<br />

Frequency<br />

AO1 = × AO1Gain<br />

+ AO1Bias<br />

MaxFreq<br />

OUT-04 AO1 Filter : sets the filter time constant of the analog output.<br />

OUT-06 AO1 Monitor : The analog output value can be monitored, which is represented in percentage on the basis<br />

of the 10V of maximum output voltage.<br />

2) 0 ~ 20mA Current Output<br />

Group Code No. Function Display<br />

Initial<br />

Setting<br />

Unit<br />

07 AO2 Mode 0 Frequency -<br />

08 AO2 Gain - 100.0 %<br />

OUT<br />

09<br />

10<br />

AO2 Bias<br />

AO2 Filter<br />

-<br />

-<br />

0.0<br />

5<br />

%<br />

Msec<br />

11 AO2 Const % - 0.0 %<br />

12 AO2 Monitor - 0.0 %<br />

Selects the items output from the AO2(Analog Output 2) terminal of the inverter terminal block and adjusts their size.<br />

The function of each code are the same as the items of 0~10V voltage output described above and the output range<br />

is 0~20mA.