Chapter 8 Applied Functions<br />

CNF-42 Changed Para: When setting as View Changed, changed parameter comparing to default value is<br />

displayed.<br />

CNF-44 Erase All Tip : deletes all the saved failure history.<br />

CNF-60 Add Title Del : this is a function to set to enable added codes in previous version to display and operate<br />

added functions when SW of inverter main body is updated with new coded. If you set this at Yes, extract the digital<br />

loader from the main body and insert it again, the title of the digital loader is updated.<br />

CNF-62 WH Count Reset : The accumulated electricity is cleared.<br />

CNF-74 Fan Time, CNF-75 Fan Time Rst : displays the cumulative time for which the cooling fan has operated. If<br />

you select Yes at CNF-75 Fan Time Rst, CNF-74 Fan Time is cleared.<br />

8.1.34 Timer function<br />

8-50<br />

Group Code No. Function Display Initial Setting Display Unit<br />

IN 65~75 Px Define 38 Timer In -<br />

31~33 Relay1,2 / Q1 27 Timer Out -<br />

OUT 55 TimerOn Delay - 3.00 Sec<br />

56 TimerOff Delay - 1.00 Sec<br />

This is the timer function of the multi-function input terminal. You can turn the multi-function output(relay included)<br />

after a certain period of time.<br />

IN-65~75 Px Define : Set the terminal to operate as the timer among multi-function input terminals at No. 38 Timer<br />

In. If you input the set terminal, the output set as Timer Out becomes active after the period of time set in OUT-55<br />

TimerOn Delay. If the multi-function input terminal is turned off, the multi-function output(or relay) is turned off after<br />

the period of time set in OUT-56 TimerOff Delay.<br />

Px(Timer In)<br />

Q1(Timer Out)<br />

Out-55<br />

Out-56