5.1 Peripheral Devices<br />

Ground<br />

5.1.1 Composition of peripheral devices<br />

Chapter 5 Peripheral Devices<br />

It is required to connect the inverter correctly by selecting proper peripheral devices. Wrong system composition or<br />

connection might impair normal operation or cause significant life span decrease. At worst, the inverter might be<br />

damaged, so use the product properly according to the manual and cautions.<br />

Ground<br />

Power Supply<br />

specification<br />

Distribution switch or<br />

short circuit switch<br />

Electric contactor<br />

(Possible to Select)<br />

AC and DC reactor<br />

(Possible to Select)<br />

<strong>Inverter</strong> installation<br />

place and Wiring<br />

<strong>Inverter</strong> output<br />

Use within the power supply specification for<br />

the inverter.<br />

200V Class:200~230V(-15%~+10%)<br />

400V Class:380~480V(-15%~+10%)<br />

High current flows in the inverter while power<br />

is supplied. Be careful when you select the<br />

switch because the inverter<br />

This does not have to be necessarily installed,<br />

but if you do, do not start or stop the inverter<br />

frequently with the contactor. It might<br />

decrease the life of the inverter.<br />

The reactor is necessary for installation where<br />

power factor improvement or input power<br />

capacity is high(over 1000kVA, distribution<br />

distance below 10m). Be careful when you<br />

select.<br />

The life of the inverter greatly affected by the<br />

surrounding temperature, make sure the<br />

temperature does not exceed the permitted<br />

range. Wrong wiring might cause damage to<br />

the product, therefore follow the installation<br />

guide. Ground terminal must be grounded.<br />

Do not connect static condenser, surge killer,<br />

radio noise filter to output. It might cause<br />

damage or failure. Ground terminal must be<br />

grounded.<br />