Chapter 11 Communication Function<br />

Monitor Registration Error Response:<br />

11-12<br />

NAK Address No. CMD Error Code SUM EOT<br />

15h “01” ~ “1F” “X” “**” “XX” 04h<br />

1 2 1 2 2 1<br />

Total byte = 9<br />

2) Monitor implementation<br />

Request for Monitor Registration Implementation:<br />

Request for reading the data of the address No. registered by monitor registration request.<br />

ENQ Address No. CMD SUM EOT<br />

05h “01” ~ “1F” “Y” “XX” 04h<br />

1 2 1 2 1<br />

Total byte = 7<br />

Monitor Registration Implementation Normal Response:<br />

ACK Address No. CMD Data SUM EOT<br />

06h “01” ~ “1F” “Y” “XXXX…” “XX” 04h<br />

1 2 1 n * 4 2 1<br />

Total byte= 7 + n * 4 = maximum 39<br />

Monitor Registration Implementation Error Response:<br />

Error Code<br />

NAK Address No. CMD Error Code SUM EOT<br />

15h “01” ~ “1F” “Y” “**” “XX” 04h<br />

1 2 1 2 2 1<br />

Total byte = 9<br />

Code Abbreviation Description<br />

01:ILLEGAL FUNCTION IF<br />

02:ILLEGAL DATA ADDRESS IA<br />

When slave cannot implement the received function. That<br />

is, when there is no appropriate function.<br />

When the received address is not valid in the slave.<br />

Parameter address, not the address No.<br />

03: ILLEGAL DATA VALUE ID When the received data is not valid in the slave.<br />

21: WRITE MODE ERROR WM Read Only or change prohibition during operation.<br />

22: FRAME ERROR FE When the frame size or internal num or sum is different.