Chapter 8 Applied Functions<br />

1) Preparation before Starting<br />

Separate the load connected to the motor axis.<br />

Motor parameter input : enter the following values shown on the motor plate.<br />

DRV-14 Motor Capacity(motor capacity)<br />

BAS-11 Pole Number(number of poles)<br />

BAS-12 Rated Slip(rated slip)<br />

BAS-13 Rated Curr(rated current)<br />

BAS-15 Rated Volt(rated voltage)<br />

BAS-16 Efficiency(efficiency)<br />

2) Check whether the encoder option card is mounted on the main body of the inverter.<br />

Set the encoder option mode(APO-01) at No.1 feedback and input the following information according to the specification<br />

of the encoder.<br />

APO-04 Enc Type Sel: select signal delivery method of encoder. Set with instruction manual of encoder.<br />

According to specifications of encoder, select one out of Line <strong>Drive</strong>r(0), Totem or Com(1), and Open Collect(2).<br />

APO-05 Enc Pulse Sel: set the way of encoder output pulse.<br />

In case of (A+B) of NO.0, select forward operation,<br />

In case of –(A+B) of NO.2, select reverse operation. Select NO.1, select frequency reference for setting.<br />

APO-06 Enc Pulse Num: input the number of pulse per rotation.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

BAS 20 Auto Tuning 3 Enc Test 0~4 -<br />

01 Enc Opt Mode 1 Feed-back 0~2 -<br />

04 Enc Type Sel 0 Line <strong>Drive</strong>r 0~2 -<br />

APO 05 Enc Pulse Sel 0 (A+B) 0~2 -<br />

06 Enc Pulse Num - 1024 10~4096 -<br />

08 Enc Monitor - - - -<br />

APO -01 Enc Opt Mode: Set as No. 1 feedback.<br />

APO -04 Enc Type Sel: Set the method to deliver a signal. Set it right, referring to the manual. Select one out of Line<br />

<strong>Drive</strong>r(0), Totem or Com(1), Open Collect(2).<br />

APO-05 Enc Pulse Sel: set the way of encoder output pulse.<br />

In case of (A+B) of NO.0, select forward operation,<br />

In case of –(A+B) of NO.2, select reverse operation. Select NO.1, select frequency reference for setting.<br />

APO-06 Enc Pulse Num: input the number of pulse per rotation.<br />

APO-08 Enc Monitor: convert encoder output to the number of motor rotation and write in unit, Hz or rpm.<br />