The following figure illustrates setting the number of automatic restarts at 2.<br />

8.1.21 Operation sound selection<br />

Group Code No. Function Display Setting Display<br />

CON<br />

Steady speed<br />

operation<br />

Frequency<br />

voltage<br />

Speed search operation<br />

reset<br />

Operating<br />

command<br />

The number of<br />

auto-restart<br />

Chapter 8 Applied Functions<br />

Setting<br />

Range<br />

04 Carrier Freq - 5.0 0.7 ~ 15 kHz kHz<br />

05 PWM Mode 1 Normal PWM<br />

Normal PWM<br />

/Low Leakage PWM<br />

CON-04 Carrier Freq : Selects the operation sound from the motor. The power device(IGBT) inside the inverter<br />

generates high frequency switching voltage to supply to the motor. Here the high frequency is called carrier<br />

frequency. The higher the carrier frequency is, the lower the operation sound generated from the motor is and the<br />

lower the carrier frequency is, the higher the operation sound is.<br />

CON-05 PWM Mode : The heat loss and leak current from the inverter can be reduced according to the load rate. If<br />

you select Normal PWM, you can reduce heat loss and leak current more than when you select Low Leakage<br />

PWM, but the motor sound increases.<br />

2 1 2 1 0 2<br />

The merits and demerits of each load rate and the carrier frequency are as follows.<br />

30s<br />

ec<br />

H27<br />

Carrier Frequency<br />

0.7 kHz 15kHz<br />

Normal PWM LowLeakage PWM<br />

Motor Noise � �<br />

Heat � �<br />

Noise � �<br />

Leak Current � �<br />

Trip<br />

Unit<br />

-<br />

8-39