Chapter 8 Applied Functions<br />

Group Code No. Function Display Setting Display Unit<br />

8-32<br />

65 Speed Lmt Gain - 100 %<br />

IN 65~75 Px Define 35 Speed/Torque -<br />

OUT<br />

2) Torque Reference Setting<br />

31~33 Relay x or Q1 27 Torque Dect -<br />

59 TD Level - 100 %<br />

60 TD Band - 5.0 %<br />

Torque reference can be set in the same way as the frequency reference. The torque control mode set, the frequency<br />

reference is not active.<br />

DRV-08 Trq Ref Src : Selects the type to use as the torque reference.<br />

0 : Keypad-1, 1 : keypad-2<br />

Input the torque reference using the keypad. The torque can be set in CON-02 Cmd Torque and up to 180% of the motor<br />

rated torque can be set.<br />

2 : V1, 3 : I1<br />

The torque reference can be input by using the voltage(V1) or current(I1) terminal block of the inverter. Set the maximum<br />

torque by using the item of IN-02 Torque at 100%. For example, if IN-02 is set at 200% and the torque reference is set with<br />

the current input(V1), you can check the setting in MON mode and select no. 19 Torque Ref from CNF-06 ~ 08.<br />

6 : Int 485<br />

Sets the torque limit by using the communication terminal of the inverter terminal block.<br />

3) Speed Limit<br />

Caution<br />

For operation in the torque control mode, the sensorless vector mode and the basic operation<br />

conditions described in the vector control mode should be set in advance.<br />

Torque control is not available during low speed regeneration region and low speed light load. Please,<br />

choose vector control.<br />

When using torque control, do not switch over commands of forward and reverse rotation are during<br />

operation. It may cause over current or deceleration error of reverse way. When controlling with vector<br />

control, please set Speed Search in case that there is possibility to operate during motor free run.<br />

(CON-71 Speed Search = set Speed Search during acceleration(0001)<br />

During operation in the torque control mode, the operating speed can go up at the maximum operating speed<br />

according to the load condition. Therefore the speed limit function is used to prevent such divergence of speed.