2) Reset Starting after a Trip<br />

Chapter 8 Applied Functions<br />

If bit 2 is set at 1 and PRT-08 RST Restart is set as Yes, acceleration is carried out to the frequency before the trip in<br />

speed search motion when the reset key(or terminal block reset) is input.<br />

3) Re-starting after an Instantaneous Interruption<br />

If the inverter input power is OFF, low voltage trip occurs and power is recovered before the internal power of the inverter is<br />

OFF, acceleration is carried out to the frequency before the low voltage trip in speed search motion.<br />

Simultaneous Starting at the Time of Power ON, Bit 4 is set at 1 and ADV-10 Power-on Run is set as Yes. If inverter input<br />

power is supplied with the inverter operating command ON, acceleration is carried out to the target frequency in speed<br />

search motion.<br />

Caution<br />

For correct operation, please set speed search when accelerating in case of operation from the load to<br />

sensorless II mode. It may cause over current trip or over load trip<br />

E.g.) Speed search in case of power recovery after instantaneous interruption<br />

Notice<br />

When input power is blocked due to the instantaneous interruption, inverter blocks output by making Low<br />

voltage trip (Lvt).<br />

If input power is recovered, frequency is output and voltage increases by PI control before Low voltage trip (Lvt)<br />

occurs.<br />

t1 : Current exceeds over the size set in ADV-61 code, voltage stops increasing and frequency decreases.<br />

t2 : Current drops under the size set in ADV-61, voltage increases again and voltage stops decreasing.<br />

Normal acceleration at the frequency before trip occurs in case of normal frequency and voltage.<br />

8-37