8.1.18 Energy saving operation<br />

<strong>Manual</strong> Energy Saving Operation<br />

Chapter 8 Applied Functions<br />

Group Code No. Function Display Setting Display Unit<br />

ADV<br />

50 E-Save Mode 1 <strong>Manual</strong> -<br />

51 Energy Save - 30 %<br />

If the inverter output current is lower than the current set in BAS-14 Noload curr (no-load current of the motor), the output<br />

voltage is reduced by the amount set at ADV-51.The standard value is the voltage before the energy saving operation<br />

starts. This is not active during acceleration and deceleration.<br />

Automatic Energy Saving Operation<br />

Group Code No. Function Display Setting Display Unit<br />

ADV 50 E-Save Mode 2 Auto -<br />

The output voltage is adjusted by automatically calculating the amount of the saved energy on the basis of the motor rated<br />

current (BAS-13) and no-load current (BAS-14).<br />

Caution<br />

Be aware that the time required for acceleration or deceleration by a change of the operating<br />

frequency or stop command during energy saving operation might be longer than the set period of<br />

time for acceleration and deceleration because of the control time it takes the energy saving<br />

operation to come back to normal operation.<br />