Chapter 13 Table of Functions<br />

Control Function Group (PAR � CON)<br />

No. Communi<br />

cation No.<br />

13-15<br />

Function Display Name Setting Range Initial Value<br />

Shift<br />

in<br />

Opera<br />

tion<br />

Page V<br />

/<br />

F<br />

1)Control Mode<br />

Bit 0000~1111<br />

1<br />

accelerating speed<br />

search selection<br />

Speed search 2 Reset start after trip<br />

71 0h1447 Speed Search operation<br />

selection<br />

3<br />

Re-start after<br />

0000<br />

instantaneous<br />

interruption<br />

X 8-36 O O O X X<br />

4<br />

Start immediately<br />

after power ON<br />

72 0h1448 SS Sup-Current<br />

speed search<br />

standard current<br />

Below 75kW 150<br />

80~200[%]<br />

Above 90kW 100<br />

O 8-36 O O X X X<br />

73 0h1449 SS P-Gain<br />

speed search<br />

proportional gain<br />

speed search<br />

0~9999 100 O 8-36 O O X X X<br />

74 0h144A SS I-Gain integral calculus<br />

gain<br />

0~9999 200 O 8-36 O O X X X<br />

75 0h144B SS<br />

Block Time<br />

Pre-speed<br />

search output<br />

block time<br />

0~60[sec] 1.0 X 8-36 O O X X X<br />

77 0h144D KEB Select<br />

energy buffering<br />

selection<br />

0<br />

1<br />

No<br />

Yes<br />

0:No X 8-34 O O O X X<br />

78<br />

Note20) 0h144E KEB Start Lev<br />

energy buffering<br />

start amount<br />

110~140[%] 125.0 X 8-34 O O O X X<br />

79 0h144F KEB Stop Lev<br />

energy buffering<br />

stop amount<br />

130~145[%] 130.0 X 8-34 O O O X X<br />

80 0h1450 KEB Gain<br />

energy buffering<br />

gain<br />

1~2000 1000 O 8-34 O O O X X<br />

82<br />

Note21) 0h1452 ZSD Frequency<br />

permanent<br />

detection<br />

frequency<br />

permanent<br />

0~10[Hz] 2.00 O 9-14 X X O X O<br />

83 0h1453 ZSD Band detection<br />

frequency band<br />

0~2[Hz] 1.00 O 9-14 X X O X O<br />

* The grey code refers to hidden code, emerging only in case of setting of the code.<br />

Note 20)<br />

CON-78~80 are displayed only when CON-77 (KEB Select) is set as “Yes”.<br />

Note 21)<br />

CON-82~83 are displayed only when DRV-09 (Control Mode) is set as “Vector”.<br />

S<br />

L<br />

V<br />

C<br />

S<br />

L<br />

T<br />

V<br />

C<br />

T