4) Frequency setting by current input into terminal block (I1 Terminal)<br />

Chapter 7 Basic Functions<br />

Group Code No. Function Display Setting Displayed Setting Range Unit<br />

DRV 07 Freq Ref Src 3 I1 - -<br />

01 Freq at 100% - 60.00 0.00~ Max Freq Hz<br />

20 I1 Monitor - 0.00 0~20 mA<br />

22 I1 Filter - 10 0~10000 msec<br />

IN<br />

23<br />

24<br />

I1 Curr x1<br />

I1 Perc y1<br />

-<br />

-<br />

4.00<br />

0.00<br />

0~20<br />

0~100<br />

mA<br />

%<br />

25 I1 Curr x2 - 20.00 0~20 mA<br />

26 I1 Perc y2 - 100.00 0~100 %<br />

31 I1 Inverting - No No/Yes -<br />

32 I1 Quantizing - 0.04 0.04~10 %<br />

Select I1 in DRV Group 07. Input current of 0~20mA into the I1 terminal of the terminal block to set frequency.<br />

IN-01 Freq at 100%: sets the operating frequency at the maximum current input. The operating frequency when the<br />

value set in IN-26 is 100% is set.<br />

E.g.1) If IN-01 is 40.00 and IN-23~26 is set at the default value, when 20mA is input into the I1 terminal, the operation<br />

is at 40.00Hz.<br />

E.g.2) If IN-26 is 50% and IN-01, 23~26 are set at the initial value, when 20mA is input into the I1 terminal, the<br />

operation is at 30.00Hz.<br />

IN-20 I1 Monitor: displays the current input into the I1 terminal. This is used for monitoring the current input at the<br />

moment.<br />

IN-22 I1 Filter: The set time refers to the time it takes the input current which has been step input to reach about 63% of<br />

the I1 value that has been step input in the inverter.<br />

IN-23 I1 Curr x1 ~ IN-26 I1 Perc y2: You can set the slope of the output frequency and offset value against the current<br />

as follows.<br />

Set Frequency<br />

IN-26<br />

IN-24<br />

IN-23<br />

IN-31 I1 Inverting: You can turn the direction of the rotation.<br />

IN-25<br />

I1 Input<br />

IN-32 I1 Qunatizing: the same as quantizing function of IN-17. See “IN-17 V1 Quantizing”on Page 7-3.<br />