3) How to set EMC Filter functions (11~22kW Products)<br />

Chapter 4 Wiring<br />

EMC filter ON/OFF set terminal is located in lower part of the 11~22KW Terminal as shown figure below. Initial set is<br />

OFF. When the green wire is connected in upper metal connection terminal, EMC filter is ON and EMC filter is OFF if it<br />

is connected in insulated connection terminal.<br />

EMC filter ON EMC filter OFF<br />

EMC filter has effect in reducing air electronic wave while being used in power source of symmetrical ground method.<br />

Be sure to use EMC filter in symmetrical ground method such as Y connection.<br />

Caution<br />

Leakage current increases while EMC filter is ON. Do not use EMC filter when the input is asymmetrical way such as<br />

Delta connection. It may cause an electric shock.<br />

1 phase is grounded<br />

in Delta connection<br />

Grounded in single<br />

phase end<br />

Insulated terminal for<br />

EMC filter OFF<br />

Metal terminal for EMC filter<br />

ON<br />

Asymmetrical Ground structure<br />

L<br />

N<br />

R(L1)<br />

S(L2)<br />

T(L3)<br />

Grounded middle tap<br />

of 1 phase in Delta<br />

connection<br />

Non-grounded 3<br />

Phase connection<br />

R(L1)<br />

S(L2)<br />

T(L3)<br />

R(L1)<br />

S(L2)<br />

T(L3)<br />

R(L1)<br />

S(L2)<br />

T(L3)<br />

4-5