3) Frequency setting by voltage input (V1 terminal) of the terminal block: V1<br />

Group Code No. Function Display Setting Displayed Unit<br />

DRV 07 Freq Ref Src 2 V1 -<br />

Chapter 7 Basic Functions<br />

Enter 10~+10V or 0~+10V using the voltage (V1) input terminal of the terminal block. If you enter -10~+10V, you can<br />

change the revolution direction of the motor according to the symbol of the voltage signals.<br />

If you enter 0~+10V,<br />

Group Code No. Function Display Setting Displayed Setting Frequency Unit<br />

DRV 07 Freq Ref Src 2 V1 - -<br />

01 Freq at 100% - 60.00 0.00~ Max Frequency Hz<br />

05 V1 Monitor - 0.00 0~10 V<br />

06 V1 Polarity 0 Unipolar Unipolar/Bipolar -<br />

07 V1 Filter - 10 0~10000 msec<br />

IN<br />

08<br />

09<br />

V1 volt x1<br />

V1 Perc adj y1<br />

-<br />

-<br />

0.00<br />

0.00<br />

0~10<br />

0~100<br />

V<br />

%<br />

10 V1 Volt x2 - 10.00 0~10 V<br />

11 V1 Perc adj y2 - 100.00 0~100 %<br />

16 V1 Inverting - No No/Yes -<br />

17 V1 Quantizing - 0.04 0.04~10 %<br />

Set No.06 of the input terminal block group (IN) at Unipolar. Enter the volume resistance into the V1 terminal by using<br />

the voltage output of the external voltage output or VR output terminal of the inverter control terminal block as follows.<br />

When connecting external power source When connecting internal power source<br />

(2) If you use 0~+10V of the external circuit,<br />

If the volume resistance is connected to the terminal block (IN-01 Freq at 100%): set the operating frequency of the<br />

maximum voltage input. Set the operating frequency of which the values set in the input terminal block function group<br />

(IN) No. 11 or 15 is 100%.<br />

E.g.1) When IN-01 is 40.00 and the default value is set to IN-16, if 10V is input into the V1 terminal, operation is at<br />

40.00Hz.<br />

V 1<br />

5G<br />

E.g.2) When IN-11 is 50% and the default value is set between IN-01 and IN-16, if 10V is input into the V1 terminal,<br />

operation is at 30.00Hz (50% of max 60Hz).<br />

VR<br />

V1<br />

5G<br />

7-2