Chapter 13 Table of Functions<br />

3.1.8 Parameter mode – Applied function group (�APP)<br />

Applied Function Group (PAR � APP)<br />

No.<br />

13-27<br />

Commu<br />

nication<br />

No.<br />

Function<br />

Display<br />

Name Setting Range<br />

Initial<br />

Value<br />

Shift in<br />

Operation<br />

Page V<br />

/<br />

F<br />

Control Mode<br />

00 - Jump Code jump code 0~99 20 O - O O O O O<br />

0 None<br />

1 Traverse<br />

01 0h1801 App Mode applied function selection<br />

2 Proc PID<br />

3 Reserved<br />

4 Auto<br />

Sequence<br />

0:<br />

None<br />

S<br />

L<br />

V<br />

C<br />

S<br />

L<br />

T<br />

V<br />

C<br />

T<br />

X - O O O X X<br />

08<br />

Note28) 0h1808 Trv Apmlit % traverse operating range 0~20[%] 0.0 O 8-53 O O O X X<br />

09 0h1809 Trv Scramb %<br />

traverse<br />

magnitude<br />

scramble<br />

0~50[%] 0.0 O 8-53 O O O X X<br />

10 0h180A Trv Acc Time traverse accelerating time 0.1~600.0[sec] 2.0 O 8-53 O O O X X<br />

11 0h180B Trv Dec Time<br />

traverse<br />

time<br />

decelerating<br />

0.1~600.0[sec] 3.0 O 8-53 O O O X X<br />

12 0h180C Trv Offset Hi traverse offset upper limit 0~20.0[%] 0.0 O 8-53 O O O X X<br />

13 0h180D Trv Offset lo traverse offset lower limit 0~20.0[%] 0.0 O 8-53 O O O X X<br />

16<br />

Note 29) 0h1810 PID Output PID output monitor [%] 0.00 - 8-12 O O O X X<br />

17 0h1811 PID Ref Value PID reference monitor [%] 50.00 - 8-12 O O O X X<br />

18 0h1812 PID Fdb Value PID feedback monitor [%] 0.00 - 8-12 O O O X X<br />

19 0h1813 PID Ref Set PID reference setting -100~100[%] 50% O 8-12 O O O X X<br />

0 Keypad<br />

1 V1<br />

2 I1<br />

3 V2<br />

20 0h1814 PID<br />

Ref Source<br />

PID reference selection<br />

4 I2<br />

5 Int 485<br />

6 Encoder<br />

7 FieldBus<br />

8 PLC<br />

9 Synchro<br />

10 Binary Type<br />

0:Key<br />

pad<br />

X 8-12 O O O X X<br />

* The grey code refers to hidden code, emerging only in case of setting of the code.<br />

Note 28) APP 08~13 codes are displayed only when APP-01 (App Mode) is set as “Traverse”.<br />

Note 29) APP 16~45 codes are displayed only when APP-01 (App Mode) is set as “Proc PID” or APP-01(App Mode) is set as “MMC” and<br />

Requl Bypass(APO-34) is set as “No”.