Chapter 10 Protective Functions<br />

10-13<br />

Set the underload ratio at an operating frequency twice the motor rated slip speed(BAS-12 Rated Slip) at PRT-27.<br />

Set the underload ratio at the base frequency (DRV-18 Base Freq) at PRT-28. If variable torque is necessary like a fan<br />

or pump, set the PRT-04 Load Duty at No. 0 Normal Duty. In case of No. 1 Heavy Duty, it is set at the load for constant<br />

torque such as elevating devices or a conveyer.<br />

PRT-26 UL Warn Time, PRT-28 UL Trip Time : The protective function becomes activated if the underload level<br />

condition described above continues for the warning time or failure time. This function is not activated during the<br />

energy saving operation (ADV-50 E-Save Mode).<br />

10.1.11 Overspeed error<br />

This function is activated when the control mode(DRV-09 Control Mode) is Vector.<br />

Group Code No. Function Display Setting Display Unit<br />

PRT<br />

PRT-30<br />

70 Over SPD Level - 60.00 Hz<br />

72 Over SPD Time - 0.01 Sec<br />

If the motor rotates faster than the overspeed frequency(Over SPD Freq) for overspeed detection time(Over SPD<br />

Time), the inverter blocks output.<br />

Output Current<br />

PRT-29<br />

Output<br />

Frequency<br />

Rated slipX2 Base Frequency<br />

Output Current<br />

PRT-30<br />

Set at normal load(Normal duty:VT)<br />

Rated Current X2 Output Frequency<br />

Set at heavy load(Heavy duty:CT)