Chapter 12 Checking and Troubleshooting<br />

12.1.2 Alarm functions<br />

12-3<br />

Over Load<br />

Under Load<br />

Inv Over Load<br />

Type Description<br />

Lost Command<br />

Fan Warning<br />

DB Warn %ED<br />

Enc Conn Check<br />

Enc Dir Check<br />

Lost Keypad<br />

An alarm signal is released in case of overload to the motor. Operation resumes if you set PRT-17 at 1. If<br />

signals are necessary for the output contact point, No. 4 overload is selected among the functions of<br />

OUT31~33.<br />

Set PRT-25 at 1 if an alarm is necessary for an underload situation. As the output signal, No. 6 Under Load<br />

is selected among the functions of OUT31~33.<br />

An alarm is released if time equal to 60% of the level at which the inverter IOLT functions is accumulated.<br />

As the output signal, No. 5 IOL is selected among the functions of OUT31~33.<br />

An alarm signal can be released as well when PRT-12 Lost Cmd Mode is 0. The alarm is released in a<br />

certain condition between PRT13~15. As the output signal, No. 12 Lost Command is selected among the<br />

functions of OUT31~33.<br />

An alarm is released if a problem is detected with the cooling fan with PRT-79 FAN Trip Mode set at 1. As<br />

the output signal, No.8 Fan Warning is selected among the functions of OUT31~33.<br />

An alarm is released if the DB resistance consumption rate is above the prescribed degree. The detection<br />

level is set at PRT-66.<br />

An alarm is signified if No. 3 Enc Test is selected from BAS-20 Auto Tuning and no signal is input during the<br />

encoder test. Signals are released if ENC Tune is set among the functions of OUT31~33.<br />

An alarm is signified if No. 3 Enc Test is selected from BAS-20 Auto Tuning and the setting is wrongly<br />

changed between encoder phase A and B during the encoder test or the rotation direction is reverse.<br />

Signals are released if ENC Dir is set among the functions of OUT31~33.<br />

An alarm is signified if the operating command is keypad or any problem is detected with the<br />

communication between the keypad and the main body of the inverter in Keypad JOG Mode with PRT-11<br />

Lost KPD Mode set 0. As the output signal, No. 29 Lost Keypad is selected among the functions of<br />

OUT31~33.