1 : Aux<br />

Chapter 8 Applied Functions<br />

The motion sequence of the auxiliary motor starts with the auxiliary motor selected in APO-21(starting auxiliary<br />

motor selection). When the cumulative operating time of a main and auxiliary motor exceeds the auto change<br />

time(APO-36), the auto change condition is met. If the main motor is stopped by a stop command or sleep operation<br />

mode after in the auto change condition, the start sequence of the auxiliary motor selected in APO-21 is changed.<br />

For example, if there are four auxiliary motors operating and No. 4 is selected in APO-21, the start sequence of the<br />

auxiliary motor automatically changes to No. 1. Therefore, the previous start sequence of the auxiliary motor of<br />

4,1,2,3 changes to 1,2,3,4 and if the condition goes back to the auto change condition, the sequence changed to<br />

2,3,4,1.<br />

2 : Main<br />

Automatic change is available without distinction between the main and auxiliary motors. The auto change condition<br />

is met if the cumulative operating time of the motor connected to the inverter output exceeds the auto change<br />

time(APO-36).<br />

R U S V T W<br />

<strong>Inverter</strong><br />

UV W<br />

R S T<br />

Main<br />

motor<br />

Auxiliary<br />

motor1<br />

3 phase input<br />

Starting sequence : auxiliary 1 ->auxiliary2 -> auxiliary3 -> auxiliary 4<br />

Stop sequence : auxiliary 4 ->auxiliary3 -> auxiliary2 -> auxiliary1<br />

KD1 KD2 KD3 KD4<br />

Auxiliary<br />

motor2<br />

Auxiliary<br />

motor3<br />

If the inverter is stopped by a stop command or sleep operation mode, the operating sequence of the motor<br />

automatically changes. For example, if the starting auxiliary motor selection(APO-21) is set at 2, the inverter output<br />

is connected to No. 2 motor. If there are four motors and the auxiliary motor operating condition is met, motors 3, 4<br />

and 1 starts operating one after another in sequence. If the inverter stops in the auto change condition, motor No. 3<br />

is connected to the inverter output in the next restart and the auxiliary motors operates in the sequence of 4, 1 and 2.<br />

Auxiliary<br />

motor4<br />

8-59