Chapter 10 Protective Functions<br />

PRT-43 ETH Cont : sets the magnitude of the current at which the electronic thermal protective function becomes<br />

active. Incessant operation is available without protection below the set value.<br />

Continuously permitted current[%]<br />

100<br />

PRT-41=1<br />

95<br />

PRT-41=0<br />

65<br />

10.1.2 Overload warning and troubleshooting (Trip)<br />

This function is for releasing an warning and troubleshooting when the motor is supplied with overload in comparison<br />

with the rated current of the motor. You can set the current magnitude for the warning and troubleshooting.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

PRT<br />

OUT<br />

04 Load Duty 1 Heavy Duty - -<br />

17 OL Warn Select 1 Yes No/Yes -<br />

18 OL Warn Level - 150 30~180 %<br />

19 OL Warn Time - 10.0 0~30 sec<br />

20 OL Trip Select 1 Free-Run - -<br />

21 OL Trip Level - 180 30~200 %<br />

22 OL Trip Time - 60.0 0~60.0 sec<br />

31 Relay 1 -<br />

32 Relay 2 5 Over Load<br />

-<br />

33 Q1 Define<br />

PRT-04 Load Duty : Select a load classification<br />

0 : Nomal Duty<br />

Set VT (Variable Torque) loads such as fan or pump (Overload endurance : 1min at 110% of VT rated current)<br />

1 : Heavy Duty<br />

Set CT (Constant Torque) loads such as hoist or crane (Overload endurance : 1min at 150% CT rated current)<br />

PRT-20 OL Trip Select : selects the inverter operation in case of an overload failure.<br />

0 : None<br />

No action is taken to protect from overload.<br />

1 : Free-Run<br />

<strong>Inverter</strong> output is blocked in case of an overload failure. The motor does free run.<br />

2 : Dec<br />

Decelerating stop in case of a failure.<br />

Frequency[Hz]<br />

20 60<br />

PRT-42<br />

PRT-43<br />

Current[%]<br />

60<br />

-<br />

Electronic thermal time(sec)<br />

-<br />

10-2