Chapter 12 Checking and Troubleshooting<br />

12-9<br />

Checkup<br />

Part<br />

Control<br />

circuit<br />

Protective<br />

circuit<br />

Cooling<br />

system<br />

Checkup<br />

items<br />

Operation<br />

checking<br />

Cooling fan<br />

Display Meter<br />

Motor<br />

Total<br />

Isolation<br />

resistance<br />

Checkup<br />

1) Check the<br />

imbalance of each<br />

output voltage<br />

during the<br />

operation.<br />

2) No abnormalities<br />

on the display circuit<br />

after executing<br />

sequence<br />

protection test<br />

1) Is there any<br />

abnormal vibration<br />

or sound?<br />

2) Is there any<br />

laxness on the<br />

connecting parts?<br />

Is the displayed<br />

value normal?<br />

1) Is there any<br />

abnormal vibration<br />

or sound?<br />

2) Is there any<br />

abnormal smell?<br />

Megger check<br />

(Between the<br />

output terminal<br />

and conneting<br />

terminal)<br />

Checkup cycle<br />

Regular<br />

daily (Year)<br />

1 2<br />

Ο<br />

Ο<br />

Ο<br />

Ο<br />

Ο Ο<br />

Ο<br />

Ο<br />

Ο<br />

Way of<br />

Checkup<br />

1) Check the<br />

voltage of the<br />

<strong>Inverter</strong> output<br />

terminal among<br />

U,V,W<br />

2) short or open the<br />

<strong>Inverter</strong> protection<br />

circuit by force.<br />

1) Turn it with<br />

hands under<br />

condition of power<br />

off<br />

2) Fasten it Again.<br />

Check the<br />

displayed value<br />

on the surface of<br />

panel<br />

1)Check by ears,<br />

eyes and hands<br />

2)Check the<br />

abnormality such<br />

as overheating,<br />

damage etc.<br />

Disconnect the<br />

connection of<br />

U,V,W and<br />

connect the moter<br />

wires.<br />

Criterion decision Counter<br />

plan<br />

1) Voltage within<br />

phases:<br />

For balance 200V<br />

(400V) - within<br />

4V(8V)<br />

2) Abnormal circuit is<br />

on the operation<br />

according to the<br />

sequence.<br />

1) It turns smoothly<br />

2) No Abnormality<br />

should be founded<br />

Check the regulational<br />

and administrative<br />

value<br />

No Abnormality should<br />

be founded<br />

Digital<br />

multimeter/<br />

rectification<br />

voltmeter<br />

voltagemeter<br />

/amperemeter<br />

Over 5MΩ 500V class<br />

Megger