Chapter 13 Table of Functions<br />

13.1.3 Parameter mode – Parameter mode – Extended function group<br />

(PAR�ADV)<br />

Extended Function Group (PAR � ADV)<br />

No.<br />

13-7<br />

Communi<br />

cation<br />

No.<br />

Function Display Name Setting Range<br />

Initial<br />

Value<br />

Shift<br />

in<br />

Oper<br />

ation<br />

Page V<br />

/<br />

F<br />

Control Mode<br />

00 - Jump Code jump code 0~99 24 O - O O O O O<br />

01<br />

02<br />

0h1301<br />

0h1302<br />

Acc Pattern<br />

Dec Pattern<br />

accelerating pattern<br />

decelerating pattern<br />

0<br />

1<br />

Linear<br />

S-curve<br />

0:Linear<br />

X<br />

X<br />

7-19<br />

7-19<br />

O<br />

O<br />

O<br />

O<br />

O<br />

O<br />

X<br />

X<br />

X<br />

X<br />

03 0h1303 Acc S Start<br />

S accelerating starting<br />

slope<br />

1~100[%] 40 X 7-19 O O O X X<br />

04 0h1304 Acc S End S accelerating end slope 1~100[%] 40 X 7-19 O O O X X<br />

05 0h1305 Dec S Start<br />

S decelerating starting<br />

slope<br />

1~100[%] 40 X 7-19 O O O X X<br />

06 0h1306 Dec S End S decelerating end slope 1~100[%] 40 X 7-19 O O O X X<br />

07 0h1307 Start Mode starting method<br />

0<br />

1<br />

Acc<br />

Dc-Start<br />

0:Acc X 7-25 O O O X X<br />

0 Dec<br />

1 Dc-Brake<br />

08 0h1308 Stop Mode stop method<br />

2 Free-Run 0:Dec X 7-26 O O O X X<br />

3 Flux Braking<br />

4 Powr Braking<br />

09 0h1309 Run Prevent<br />

rotation preventing<br />

direction selection<br />

0<br />

1<br />

2<br />

None<br />

Forward Prev<br />

Reverse Prev<br />

0:Non<br />

e<br />

X 7-14 O O O X X<br />

10 0h130A Power-on Run power input starting<br />

0<br />

1<br />

No<br />

Yes<br />

0:No O 7-15 O O O X X<br />

12<br />

Note8) 0h130C Dc-Start Time starting DC braking time 0~60[sec] 0.00 X 7-25 O O O X X<br />

13 0h130D Dc Inj Level DC supply 0~200[%] 50 X 7-25 O O O X X<br />

14<br />

Note9) 0h130E Dc-Block Time<br />

Pre-DC braking output<br />

block time<br />

0~60[sec] 0.10 X 7-26 O O O X X<br />

15 0h130F Dc-Brake Time DC braking time 0~60[sec] 1.00 X 7-26 O O O X X<br />

16 0h1310 Dc-Brake Level DC braking 0~200[%] 50 X 7-26 O O O X X<br />

17 0h1311 Dc-Brake Freq DC braking frequency<br />

startingfrequency~<br />

60[Hz]<br />

5.00 X 7-26 O O O X X<br />

20 0h1314 Acc Dwell Freq<br />

Accelerating dwell<br />

frequency<br />

Starting frequency<br />

~maximum<br />

frequency[Hz]<br />

5.00 X 8-9 O O O X X<br />

21 0h1315 Acc Dwell Time<br />

Accelerating dwell<br />

operation time<br />

0~60.0[sec] 0.00 X 8-9 O O O X X<br />

22 0h1316 Dec Dwell Freq<br />

Decelerating dwell<br />

frequency<br />

Starting frequency<br />

~maximum<br />

frequency[Hz]<br />

5.00 X 8-9 O O O X X<br />

23 0h1317 Dec Dwell Time<br />

Decelerating dwell<br />

operation time<br />

0~60.0[sec] 0.00 X 8-9 O O O X X<br />

* The grey code refers to hidden code, emerging only in case of setting of the code.<br />

Note 8)<br />

ADV-12 is displayed only when ADV-07 “Stop Mode” is set as “Dc-Start”.<br />

Note 9)<br />

ADV-14~17 is displayed only when ADV-08 “Stop Mode” is set as “DC-Brake”.<br />

S<br />

L<br />

V<br />

C<br />

S<br />

L<br />

T<br />

V<br />

C<br />

T