11.2.3 Detailed writing protocol<br />

Writing Request:<br />

ENQ Address No. CMD Address<br />

No.<br />

Number of<br />

Addresses<br />

Chapter 11 Communication Function<br />

Data SUM EOT<br />

05h “01” ~ “1F” “W” “XXXX” “1” ~ “8” = n “XXXX…” “XX” 04h<br />

1 2 1 4 1 n * 4 2 1<br />

Total byte = 12 + n * 4 = 44 at maximum<br />

Normal Writing Response:<br />

ACK Address No. CMD Data SUM EOT<br />

06h “01” ~ “1F” “W” “XXXX…” “XX” 04h<br />

1 2 1 n * 4 2 1<br />

Total byte = 7 + n * 4 = 39 at maximum<br />

Error Writing Response:<br />

NAK Address No. CMD Error Code SUM EOT<br />

15h “01” ~ “1F” “W” “**” “XX” 04h<br />

1 2 1 2 2 1<br />

Total byte = 9<br />

11.2.4 Monitor registration detailed protocol<br />

1) Monitor registration<br />

Monitor Registration Request:<br />

Monitor registration is the function of periodically updating data with designating the data in advance which need monitoring<br />

continuously.<br />

Request for registration of n number of address No. (not necessarily consecutive)<br />

ENQ Address No. CMD<br />

Number of<br />

Addresses<br />

Address No. SUM EOT<br />

05h “01” ~ “1F” “X” “1” ~ “8”=n “XXXX…” “XX” 04h<br />

1 2 1 1 n * 4 2 1<br />

Total byte = 8 + n * 4 = Maximum 40<br />

Monitor Registration Normal Response:<br />

ACK Address No. CMD SUM EOT<br />

06h “01” ~ “1F” “X” “XX” 04h<br />

1 2 1 2 1<br />

Total byte = 7<br />