14.11.2012 Views

SV-iS7 User Manual - Inverter Drive Supermarket

SV-iS7 User Manual - Inverter Drive Supermarket

SV-iS7 User Manual - Inverter Drive Supermarket

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

1) Speed Command Loss<br />

Chapter 10 Protective Functions<br />

If the speed is set by analog input from the terminal block, communication option or the keypad, the action of the inverter can be<br />

selected when the speed command is lost due to severance of the signal line and so on.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

PRT<br />

12 Lost Cmd Mode 1 Free-Run - -<br />

13 Lost Cmd Time - 1.0 0.1~120 Sec<br />

14 Lost Preset F - 0.00 Starting Freq~Max. Freq Hz<br />

15 AI Lost Level 1 Half of X1 - -<br />

OUT 31~33 Relay1,2, Q1 13 Lost Command - -<br />

PRT-12 Lost Cmd Mode : Selects the action of the inverter in case of speed command loss.<br />

Setting Items Functions<br />

0 None<br />

The speed command is directly operating frequency without protective<br />

actions.<br />

1 Free-Run The inverter blocks output with the motor in free run.<br />

2 Dec Decelerating stop for the time set at PRT-07<br />

3 Hold Input<br />

Continues to operate at the average value of the input for the last 10 seconds<br />

until the moment that the speed command loss was detected.<br />

4 Hold Output<br />

Continues to operate at the average value of the output for the last 10<br />

seconds until the moment that the speed command loss was detected.<br />

5 Lost Preset Operates at the frequency set at PRT-14 Lost Preset F.<br />

PRT-15 AI Lost Level, PRT-13 Lost Cmd Time : sets the criterion voltage of speed command loss and judgment<br />

time for analog input.<br />

1 : Half of X1<br />

If the input signals remain the same for the time set at PRT-13 Lost Cmd Time(speed loss judgment time) with them being a half of<br />

the minimum set value of the analog input set as the speed command(DRV-07 Freq Ref Src), the protective action begins. The<br />

standard value is what is set at IN-08, IN-12, IN-23 of the terminal block input group. For example, if the speed command is set as<br />

No. 2 V1 at DRV-07 Freq Ref Src and IN-06 V1 Polarity is set as No. 0 Unipolar, the protective action starts when the voltage input<br />

is below a half of the value set at , IN-08 V1 Volt x1.<br />

2 : Below X1<br />

If a signal lower than the minimum set vale of the analog input set as the speed command continues for the time set in PRT-13<br />

Lost Cmd Time(speed loss judgment time), the protective action starts. The standard values are IN-08, IN-12 and IN-23 of the<br />

terminal block input group.<br />

10-10