Chapter 7 Basic Functions<br />

(1) ADV-24 Freq Limit: If you set the frequency as Yes with the initially set value being No, you can set the<br />

frequency only between the upper limit(ADV-25) and lower limit(ADV-26). With frequency set as No, ADV-25 and<br />

ADV-26 codes are not displayed.<br />

(2) ADV-25 Freq Limit Lo, ADV-26 Freq Limit Hi: sets the upper and lower limits. The minimum set value of the<br />

upper limit is the lower limit and the maximum value of the lower limit is the upper limit.<br />

Upper Limit<br />

Frequency<br />

Lower Limit<br />

10V V1(Voltage Input)<br />

0 20mA I (Current Input)<br />

3) Frequency Jump (Avoiding mechanical resonant frequency)<br />

Frequency jump is for prohibiting frequency setting so that the inverter does not operate in the resonant frequency<br />

band which might occur to the user’s device system. The frequency passes through the frequency jump band when<br />

the motor accelerates or decelerates and cannot be set within the set frequency jump band.<br />

Group Code No. Function Display Initial Setting Display Setting Range Unit<br />

27 Jump Freq 0 --- No ---- No/Yes -<br />

28 Jump Lo 1 10.00 0~Jump Freq Upper Limit 1 Hz<br />

29 Jump Hi 1 15.00<br />

Jump Freq Lower Limit 1<br />

~Max Freq<br />

Hz<br />

ADV<br />

30 Jump Lo 2 20.00 0~Jump Freq upper Limit 2 Hz<br />

31 Jump Hi 2 25.00<br />

Jump Freq Lower Limit 2<br />

~Max Freq<br />

Hz<br />

32 Jump Lo 3 30.00 0~Jump Freq Upper Limit 3 Hz<br />

33 Jump Hi 3 - 35.00<br />

Jump Freq Lower Limit 3<br />

~Max Freq<br />

Hz<br />

If you want to increase the frequency, if the set frequency(current, voltage, RS485 communication, keypad setting,<br />

etc.) is within the jump frequency band, keep the frequency jump lower value and raise the frequency after the set<br />

frequency goes out of the frequency jump band.<br />

No Upper/Lower Limit<br />

to Frequency<br />

Max Frequency<br />