Chapter 10 Protective Functions<br />

10-15<br />

If the internal DC voltage goes down below a certain degree because of the inverter input voltage being blocked, the<br />

inverter blocks output and displays low voltage failure(Low Voltage). If PRT-81 LVT Delay time has been set, in case of<br />

a low voltage failure, the inverter output is blocked and it is handled as a failure after the set period of time.<br />

A warning signal of a low voltage failure can be released using multi-function output or relay. However, in case of a<br />

warning signal, the LVT Delay time does not apply.<br />

10.1.16 Output blocking by multi-function terminal<br />

Group Code No. Function Display Setting Display Unit<br />

IN 65~75 Px Define 5 BX -<br />

If you set the function of the multi-function output terminal at No. 2 BX and input it during operation, the inverter blocks<br />

output and displays BX on the keypad display. The information on the frequency and current at the time of BX input is<br />

to be monitored.<br />

Acceleration resumes when the BX terminal is OFF with an operating command input.<br />

10.1.17 How to terminate failure state<br />

Group Code No. Function Display Setting Display Unit<br />

IN 65~75 Px Define 3 RST -<br />

To terminate the failure state, press the Reset key on the keypad or use the multi-function input terminal. The failure<br />

state is terminated if you input the terminal in case of a failiure after setting the function of the multi-function input<br />

terminal at No. 2 RST.<br />

10.1.18 Selection of action in case of option card failure<br />

Group Code No. Function Display Setting Display Unit<br />

PRT 80 Opt Trip Mode<br />

0 None<br />

1 Free-Run<br />

2 Dec<br />

1:Free-Run<br />

If there is a problem with the communication between the option card and the main body of the inverter or the option<br />

card is separated from during operation, select the inverter action status. In case of No. 1 Free-Run, the inverter output<br />

is blocked and the failure information is displayed on the keypad. In case of No. 2 Dec, it decelerates at the value set in<br />

PRT-07.