Frequency<br />

Voltage<br />

Current<br />

Operating<br />

Command<br />

ADV-17<br />

ADV-14 ADV-15<br />

2) Free Run Stop<br />

Group Code No. Function Display Setting Display Unit<br />

ADV 08 Stop mode 2 Free-Run -<br />

Chapter 7 Basic Functions<br />

Operating command off, the inverter output is blocked. Be careful that the motor might continue rotating due to the<br />

load inertia if the inverter output is blocked during high speed operation when the motor load has high inertia.<br />

3) Flux Braking (Reducing decelerating time further without braking resistance or braking Unit)<br />

Group Code No. Function Display Setting Display Unit<br />

ADV 08 Stop Mode 3 Flux Braking -<br />

If the decelerating time is short, over voltage trip might be caused by the regenerative energy from the motor. If you<br />

apply flux braking, the decelerating time can be shortened because the regenerative energy is consumed by the<br />

motor. However, be careful that damage might occur because of overheat of the motor if flux braking is applied to<br />

loads which frequently decelerates.<br />

ADV-16<br />

Frequency, Voltage<br />

Operating<br />

Command<br />

Caution<br />

When D.C. Braking is big or control time is too long,<br />

overheating and malfunction may occur.<br />

Caution<br />

Since D.C Braking is a standard of rating current for pre-set<br />

motor, please do not set over value of current of inverter’s<br />

rating current. It may cause overheating and malfunction.<br />

Caution<br />

Do not use this function in case of load with frequent deceleration. It may cause overheating of the<br />

motor and malfunction.<br />

Caution<br />

Stall prevention and Flux Braking are available only in case of deceleration. And, Flux Braking has a<br />

priority. That means that Flux Braking operates when BIT3 of PRT-50 and Flux Braking of BAS-08<br />

are set. In case of that deceleration time is too short or inertia is too big, over voltage trips may<br />

occur.<br />

7-27