Chapter 7 Basic Functions<br />

4) Operating Command by RS-485 Communication: Int 485<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

DRV 06 Cmd Source 3 Int 485 - -<br />

COM<br />

04 Int485 St ID - 1 0~250 -<br />

05 Int485 Proto 0 ModBus RTU - -<br />

06 Int485 BaudR 3 9600 1200~38400 bps<br />

07 Int485 Mode 0 D8 / PN / S1 - -<br />

You can control the inverter through communication with a higher controller (PLC or PC) by using terminal RS485 (+S,<br />

-S) on the terminal block if you set DRV-06 Cmd Src at Int 485. For details, see Communication Functions, Chapter<br />

11.<br />

7.1.6 Local/Remote by-pass operation using multi-function keys<br />

(Checking the inverter operation or equipment without changing the existing parameter setting)<br />

Group Code No. Function Display Setting Display Unit<br />

CNF 42 Multi-Key Sel 1 Local/Remote -<br />

DRV 06 Cmd Source 1 Fx/Rx-1 -<br />

Caution<br />

Local/remote By-pass operation might cause a problem with the device such as<br />

interruption during operation if it is improperly used, so it is highly recommended that<br />

you use it only when necessary.<br />

In case of operation by other than using the keypad (terminal block or communication), you can use it when checking<br />

the operation or body of the inverter or conducting manual switching operation using the keypad in the field in case of<br />

an emergency.<br />

1) Definition of Local: Local refers to the function of transforming all the operating, frequency and torque commands for<br />

them to be operated by using the keypad in order to enable the keypad to carry out all operation. In such a case, JOG<br />

command is ignored (When RUN Enable is set in the multi-function terminal, operation is possible with it on).<br />

2) Definition of Remote: Remote refers to the operation of the inverter by the previously set operating and frequency<br />

commands of the inverter in communication or sequence when it is set at communication or sequence respectively.<br />

3) CNF-42 Multi-Key Sel: If you set at No. 1 Local/Remote, the signal R emerges on the keypad status display and the<br />

multi-function keys operate in local/remote functions. When R is seen on the keypad status display, you are in the<br />

Remote Operation Mode, which operates by the previously set parameters without any change in the operation. If you<br />

want Local Operation Mode, with R displayed in the keypad status display, press the multi-function key and R turns<br />

into L and you can operate the inverter with FWD and REV keys on the keypad setting. If you press the multi-function<br />

key one more time, R is displayed and the inverter operates by the method selected in DRV-06 Cmd Source.<br />

7-13