Chapter 8 Applied Functions<br />

The output frequency of the inverter goes through PID control in order to control the system process including the flow,<br />

temperature and tension and so on.<br />

APP-01 App Mode(application mode) : You can set the process PID functions by setting at No. 2 Proc PID(Process<br />

PID).<br />

APP-16 PID Output : Displays the present output value of the PID controller with the unit, gain and scale set in APP-42,<br />

APP-43 and APP-44 reflected.<br />

APP-17 PID Ref Value : Displays the currently set reference of the PID controller with the unit, gain and scale set in APP-<br />

42, APP-43 and APP-44 reflected.<br />

APP-18 PID Fdb Value : Displays the present feedback input of the PID controller with the unit, gain and scale set in<br />

APP-42, APP-43 and APP-44 reflected.<br />

APP-19 PID Ref Set : The reference value can be input if the reference type(APP-20) of PID control is set as<br />

keypad(0:Keypad). If the reference type is set at values other than the keypad, the value set in APP-19 is ignored.<br />

APP-20 PID Ref Source : Selects the reference input of PID control(the items marked in grey are supposed to be<br />

provided soon in the future). If the V1 terminal is set as PID F/B Source, V1 cannot be set as the PID Ref Source. If F/B<br />

Source is changed to another item, V1 can be set as Ref Source.<br />

Setting Type Function PID F/B Source possibility<br />

0 Keypad Inputs the PID reference on the inverter keypad. X<br />

1 V1 -10~10V voltage input terminal of the terminal block O<br />

2 I1 0~20mA current input terminal of the terminal block O<br />

3 V2 Voltage input terminal of the extended I/O option card O<br />

4 I2 Current input terminal of the extended I/O option card O<br />

5 Int. 485 RS485 input terminal of the terminal block O<br />

6 Encoder Pulse input of the encoder option card O<br />

7 FieldBus<br />

Communication command by communication option<br />

card<br />

O<br />

8 PLC Command by PLC option card O<br />

9 Synchro Command by synchronized operation option card O<br />

10 Binary Type Command by BCD option card X<br />

The set PID reference can be displayed in the monitor mode and APP-17 and monitored in the items set as No. 17 PID<br />

Ref Value among CNF-06~08 of CNF.<br />

APP-21 PID F/B Source : Selects the feedback input of PID control. This can be selected in the inputs other than the<br />

keypad input(Keypad-1, Keypad-2) in the reference input type. The feedback cannot be set as the same input as selected<br />

in the reference.<br />

8-13