Caution<br />

Chapter 7 Basic Functions<br />

When using this function, if you reset the inverter in the terminal block of loader after a<br />

trip, the motor starts rotating. Be careful of an accident.<br />

7.1.10 Setting of accelerating/decelerating time and pattern<br />

1) Setting of accelerating/decelerating time on the basis of the maximum frequency<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

03 Acc Time -<br />

Below 75kW<br />

Above 90kW<br />

20.0<br />

60.0<br />

0~600 sec<br />

DRV<br />

04 Dec Time -<br />

Below 75kW<br />

Above 90kW<br />

30.0<br />

90.0<br />

0~600 sec<br />

20 Max Freq - 60.00 0~400 Hz<br />

BAS<br />

Frequency<br />

Reset<br />

Operating<br />

Command<br />

08 Ramp T Mode 0 Max Freq Max Freq/Delta Freq -<br />

09 Time scale 1 0.1 0.01/0.1/1 sec<br />

If you set BAS-08 at Max Freq, you can accelerate or decelerate at an equal slope on the basis of the maximum<br />

frequency regardless of the operating frequency.<br />

The acceleration time set in DRV-03 is the time it takes the frequency to reach the maximum value from 0 Hz and the<br />

deceleration time of 04 is the time it takes the frequency to stop at 0 Hz from the maximum frequency.<br />

E.g.) If you set the maximum frequency at 60.00 Hz, Acc/Dec time at 5 seconds and operating frequency at 30 Hz,<br />

the time required is 2.5 seconds.<br />

Max Frequency<br />

Frequency<br />

FX<br />

When PRT-08=0<br />

Accel Time Decel Time<br />

When PRT-08=1<br />

7-16