10 : Over Voltage (over voltage failure)<br />

Active if the inverter DC power voltage goes up above the protective action voltage.<br />

11 : Low Voltage (low voltage failure)<br />

Active if the inverter DC power voltage goes down below the low voltage protective action level.<br />

12 : Over Heat (inverter cooling fan overheat)<br />

Active if the inverter cooling fan is overheated.<br />

13 : Lost Command (command loss)<br />

Chapter 9 Monitor Functions<br />

Active in case of loss of the analog input terminal and RS485 communication command of the inverter terminal block.<br />

The communication option and extended I/O option card are mounted and it operates also in case of loss of the<br />

analog input terminal and communication command within the option.<br />

14 : RUN (running)<br />

Active while the inverter produces voltage with given operating command. It is not active during DC braking.<br />

15 : Stop (stop)<br />

Active when the operating command is OFF and there is no inverter output voltage.<br />

16 : Steady (steady speed operation)<br />

Active during steady speed operation.<br />

17 : <strong>Inverter</strong> Line (inverter operation), 18 : Comm Line (normal power operation)<br />

If normal exchange operation is necessary, they can be used as the signal sources for operation of the system<br />

sequence relay or magnetic contactor. They use the auxiliary relay of the inverter terminal block(Aux Relay) and<br />

multi-function output(MO1) and set one of the multi-function input terminals as the normal exchange. For details, see<br />

Chapter8 Applied Functions 8.1.24 By pass operation.<br />

Group<br />

Frequency<br />

Q1<br />

Operating<br />

command<br />

Code<br />

No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

IN 65~72 Px Define 16 Exchange -<br />

OUT<br />

32<br />

33<br />

Relay 2<br />

Q1 Define<br />

15<br />

16<br />

<strong>Inverter</strong> Line<br />

Comm Line<br />

-<br />

-<br />

19 : Speed Search (speed search)<br />

Active while the inverter operates for speed search. For details about the speed search, see Chapter8 Applied<br />

9-13