Chapter 11 Communication Function<br />

11-4<br />

11.1.5 Operating command and Frequency setting<br />

Group Code No. Function Display Setting Display Unit<br />

DRV<br />

06 Cmd Source 3 Int 485 -<br />

07 Freq Ref Src 7 Int 485 -<br />

DRV-06, 07: If you select Int 485 No. 3 and 7 as above, you can set the operating command and frequency in the<br />

parameter located in the common area by using the communication function.<br />

11.1.6 Command loss protection<br />

Judgment standard and Protection in case of a problem with the communication for a certain period of time<br />

Group Code No. Function Display Setting Display Unit<br />

PRT<br />

12 Lost Cmd Mode 1 Free-Run -<br />

13 Lost Cmd Time - 1.0 Sec<br />

14 Lost Preset F - 0.00 Hz<br />

OUT 31~33 Relay1,2, Q1 12 Lost Command -<br />

PRT-12 Lost Cmd Mode, PRT-13 Lost Cmd Time: selects the movement of the inverter when there is a<br />

communication problem with PRT-13 for more than an hour.<br />

Setting Item Function<br />

0 None<br />

Speed command is directly the operating frequency without<br />

protective movements.<br />

1 Free-Run The inverter blocks output. The motor continues free run.<br />

2 Dec Decelerating stop<br />

3 Hold Input<br />

4 Hold Output<br />

Continues to operate at the entered speed command until before<br />

speed loss<br />

Continues to operate at the operating frequency until before speed<br />

loss<br />

5 Lost Preset Operates at the frequency set at PRT-14 Lost Preset F.