Chapter 7 Basic Functions<br />

3) Setting of Acc/Dec Time Using Multi-Function Terminal<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

DRV<br />

03<br />

04<br />

Acc Time<br />

Dec Time<br />

-<br />

-<br />

Below 75 kW<br />

Above 90 kW<br />

Below 75 kW<br />

Above 90 kW<br />

20.0<br />

60.0<br />

30.0<br />

90.0<br />

0~600<br />

0~600<br />

sec<br />

sec<br />

BAS<br />

70~74<br />

71~75<br />

Acc Time-x<br />

Dec Time-x<br />

-<br />

-<br />

x.xx<br />

x.xx<br />

0~600<br />

0~600<br />

sec<br />

sec<br />

65~75 Px Define 11 XCEL-L - -<br />

IN 65~75 Px Define 12 XCEL-M - -<br />

89 In Check Time - 1 1~5000 msec<br />

* Acc Time-x : Acc Time-1~3, Dec Time-x: Dec Time-1~3<br />

You can change the Acc/Dec time using the multi-function terminal.<br />

Set the Acc/Dec time-0 I DRV-03 and 04 and set the Acc Time 1~3, Dec Time 1~3 in 70~75.<br />

Select the terminal to use as sequential Acc/Dec time command among the multi-function terminals P1~P11 and set<br />

each of the sequential Acc/Dec command (XCEL-L, XCEL-M). XCEL-L and XCEL-H are identified in binary codes and<br />

the operation is based on the Acc/Dec time set in BAS-70 ~ BAS-75.<br />

If you set multi-function terminals P7 and P8 at XCEL-L and XCEL-M respectively, the operation is shown as follows.<br />

Acc 3<br />

Acc 2<br />

Acc 1<br />

Dec0<br />

Dec1<br />

Dec2<br />

Acc 0<br />

Frequency<br />

Dec3<br />

P7<br />

P8<br />

FX<br />

Acc/Dec Time P8 P7<br />

0 - -<br />

1 - �<br />

2 � -<br />

3 � �<br />

IN-89 In Check Time: You can set In Check Time within the inverter when you use the multi-function input terminal as<br />

sequential Acc/Dec setting. For example, if you set the In Check Time at 100msec and input multi-function terminal P6,<br />

check another terminal block input for 100msec. After 100msec, the Acc/Dec time corresponding to P6 terminal is set.<br />

4) Change of Acc/Dec Time by Acc/Dec Time Switching Frequency Setting<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

DRV<br />

03<br />

04<br />

Acc Time<br />

Dec Time<br />

-<br />

-<br />

10.0<br />

10.0<br />

0~600<br />

0~600<br />

sec<br />

sec<br />

BAS<br />

70<br />

71<br />

Acc Time-1<br />

Dec Time-1<br />

-<br />

-<br />

20.0<br />

20.0<br />

0~600<br />

0~600<br />

sec<br />

sec<br />

ADV 60 Xcel Change Fr - 30.00 0~Max. Freq. Hz/RPM<br />

7-18