Chapter 7 Basic Functions<br />

7.1.16 Selection of starting method (When you want to change starting method)<br />

If an operating command is input in the static state, you can select the inverter starting method.<br />

Group Code No. Function Display Setting Display Initial Setting Display Unit<br />

ADV<br />

07 Start mode<br />

0<br />

1<br />

Accel<br />

DC-Start<br />

0: Accel -<br />

12 Dc-Start Time - 0.00 - 0~60<br />

13 Dc Inj Level - 50 - 0~200<br />

1) Accelerating Start<br />

Group Code No. Function Display Setting Display Unit<br />

ADV 07 Start mode 0 Accel -<br />

This is a normal accelerating method, which directly accelerates to the target frequency if the operating command is<br />

given when no particular function is selected.<br />

2) Start after D.C. Braking<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

ADV<br />

Frequency<br />

Voltage<br />

Operating<br />

Command<br />

07 Start Mode 1 Dc-Start -<br />

12 Dc-Start Time - 0.00 0~60 sec<br />

13 Dc Inj Level - 50 0~200 %<br />

ADV-12<br />

Accelerates after the D.C. voltage is supplied to the motor for the set period of time. It can be accelerated after<br />

stopping revolution of the motor by D.C. Braking when the motor is revolving before voltage is output from inverter.<br />

Also, it can be used in case of using machine braking to motor’s spindle and that some torque is needed after opening<br />

machine braking.<br />

t<br />

ADV-13<br />

Caution<br />

Do not set over inverter rating current because DC break<br />

depends on the motor rating current which is set. It may<br />

cause overheating and malfunction.<br />

Caution<br />

When D.C. Braking is big or control time is too long, overheating and malfunction may occur.<br />

Caution<br />

Since D.C Braking is a standard of rating current for pre-set motor, please do not set over value of inverter’s<br />

rating current. It may cause overheating and malfunction.<br />