7 Data Services <strong>Tightening</strong> Technology | Bosch <strong>Rexroth</strong> AG 165/3167.6 DeviceNet communicationTRTRMain Hauptstrang lineStub Stichleitung lineDeviceNet-TeilnehmerparticipantTRFigure 7–57:Termination Abschlusswiderstand resistor of main des lineHauptstrangsSchematic example of a DeviceNet networkThe network structure in DeviceNet is determined by the following maximum conditions:– The line lengths of the two furthest connected DeviceNet participants may not exceed the followingvalue:Table 7–42: Maximum permissible line lengths between two DeviceNet participantsData rateMaximum lengthFlat cable Round cable (thick) Round cable (thin)125 kbit/s 420m 500m 100m250 kbit/s 200m 250m 100m500 kbit/s 75 m 100 m 100 m– The total of all stub lines (cumulative) in the network may not exceed the following value:Table 7–43: Maximum total length of all stub linesData rateMaximum total length of all stub lines125 kbit/s 156 m250 kbit/s 78 m500 kbit/s 39 m– Both ends of the main line must be equipped with a termination resistor. The termination resistor(121 ohm, 1%, 1/4 watt) connects the CAN_H (white) and CAN_L (blue) wires.<strong>System</strong> <strong>350</strong> | 3 608 878 040/05.2008