23.03.2017 Views

wilamowski-b-m-irwin-j-d-industrial-communication-systems-2011

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

59-4 Industrial Communication Systems<br />

LN InClass DataObject CDC M/O<br />

. . .<br />

CSWI1 CSWI Mod INC M<br />

M<br />

M<br />

M<br />

Beh INS<br />

Health INS<br />

NamPlt LPL<br />

Loc SPS O<br />

OpCntRs INS O<br />

Pos DPC M<br />

PosA DPC O<br />

PosB DPC O Controls<br />

PosC DPC O<br />

OpOpn ACT O<br />

OpCls ACT O<br />

. . .<br />

Pos-This data is accessed when performing a switch command<br />

or to verify the switch status or position<br />

Common LN<br />

information<br />

FIGURE 59.3<br />

are shown).<br />

Data objects of the logical node CSWI1 data (the mandatory and the optional data attributes<br />

InClass Data CDC M/O<br />

CSWI<br />

Pos<br />

PosA<br />

. . . . . . . .<br />

DPC<br />

DPC<br />

M<br />

O<br />

Controls<br />

Attr. Name Value range M/O<br />

ctlVal<br />

stVal<br />

q<br />

t<br />

ctlModel<br />

Off/On<br />

Interm.-state/off/<br />

on/bad-state<br />

AC_CO_M<br />

M<br />

M<br />

M<br />

M<br />

ctlVal-Determines the control activity.<br />

stVal-Level of the supervised value, which starts a dedicated action<br />

of the related function.<br />

q-Quality of the attribute(s) representing the value of the data.<br />

t-Timestamp of the last change in one of the attribute(s) representing<br />

the value of the data or in the q attribute.<br />

ctlmodel-Specifies the control model of IEC 61850-7-2 that corresponds<br />

to the behavior of the data.<br />

FIGURE 59.4<br />

The common data class DPC and its attributes.<br />

CSWI1-node within the IED. If the operation is permitted, then the AC-switch is activated through an<br />

output signal. The IED then supervises the return information from the switch. If the operation terminates<br />

with success, a command termination message will be then sent. The sequence of commands and<br />

responses is standardized in IEC 61850-7-2.<br />

59.4 Communication Services<br />

The <strong>communication</strong> services for an IED are described in the <strong>communication</strong> model by the so-called<br />

abstract <strong>communication</strong> services (Figure 59.5). These services must be implemented in an IED by using<br />

standardized protocols, (SCSM).<br />

© <strong>2011</strong> by Taylor and Francis Group, LLC