Operation<br />
3-2<br />
NOTE<br />
It is recommended that you save a configuration<br />
file to disk, from the Companion software<br />
program or from the <strong>Recorder</strong>, to ensure<br />
that a copy of the configuration is<br />
available. If a failure should occur in the<br />
<strong>Recorder</strong> configuration, a new configuration<br />
file can be down-loaded from the disk.<br />
D. INITIALIZE DATABASE - Three forms of initialization<br />
may be performed on the Profile database,<br />
Smart Init, Full Init., and Erase Config. You<br />
will not typically see these options unless the unit is<br />
being powered up for the first time, or the unit finds<br />
an error in the database. These conditions can be<br />
manually invoked using the Hidden menu.<br />
1. SMART INIT - Smart Initialization verifies that<br />
each Profile database block has a correct checksum<br />
and (if incorrect) each parameter in the corrupt<br />
block(s) is verified to be within allowable<br />
boundaries. Only those parameters in corrupt<br />
blocks found to be outside these boundaries are<br />
changed. Bad parameters are always replaced<br />
with pre-defined defaults.<br />
2. FULL INIT - If you answer NO to "Smart init?",<br />
a choice is presented to force the recorder to do<br />
a "Full init?". Full initialization will completely<br />
clear all user-defined parameters, setting them to<br />
pre-defined defaults.<br />
3. Erase Config - This option is used on first time<br />
power up and will not normally be seen by you<br />
unless the database has been corrupted or this<br />
option is called from the System menu. This option<br />
will clear all variables to zero, and should be<br />
used to clear memory before programming for<br />
the first time, or after an upgrade of the software.<br />
4. INIT DEFAULTS - The listing below gives the<br />
default parameters that are used by both Smart<br />
and Full initialization:<br />
<strong>Display</strong> Block<br />
Power-up <strong>Display</strong> Mode= Unit Tag<br />
<strong>Display</strong> Rate= 1 second<br />
Time Format= American<br />
Language= English<br />
Scan Block<br />
Alarm Contact Outputs= Open on Clear, No Reflash, Failsafe<br />
off, Open on ACK,<br />
Alarm Checks= Enabled<br />
TCBO Test Interval= 300 Seconds (5 minutes)<br />
Serial Port<br />
Serial port= Set to Modbus RTU, 9600, 8bits,<br />
parity off, 2 stops<br />
Chart Scales Block<br />
For Each Scale...<br />
Scale Type= Linear<br />
Origin= Left<br />
Decimal Fix= 3 places<br />
Scale= Low= 0.0 Mid= 50.0 High= 100.0<br />
Engineering Units= Set to all spaces (cleared)<br />
Active Scaleset= Set to scaleset 1<br />
Bargraph/Pens Block<br />
Pen Assignments= Set to: Pen 1 = point 1<br />
Pen 2 = point 2<br />
Pen 3 = point 3<br />
Pen 4 = point 4<br />
Pen 5 = point 5<br />
Pen 6 = point 6<br />
Bar Assignments= Set to: Bar 1 = point 1<br />
Bar 2 = point 2<br />
Bar 3 = point 3<br />
Bar 4 = point 4<br />
Bar 5 = point 5<br />
Bar 6 = point 6<br />
Digital Assignments= Set to: Digital 1 = point 1<br />
Digital 2 = point 2<br />
Digital 3 = point 3<br />
Digital 4 = point 4<br />
Digital 5 = point 5<br />
Digital 6 = point 6<br />
<strong>Display</strong> Chart Speed Block<br />
Unit Tag= Set to "Unit Tag"<br />
Chart Speed= Standard; High Speed; No<br />
AutoSpeed change on alarm<br />
Lo Chart Speed= 60"/hr<br />
Hi Chart Speed= 60"/hr<br />
Passcode Protection Block<br />
Program Key Passcode= Set to None<br />
Function Key Passcode= Set to None<br />
Siemens AG C79000-G7374-C211-01<br />
<strong>SIREC</strong> D Manual