SIREC D Display Recorder 7ND4000
SIREC D Display Recorder 7ND4000
SIREC D Display Recorder 7ND4000
Erfolgreiche ePaper selbst erstellen
Machen Sie aus Ihren PDF Publikationen ein blätterbares Flipbook mit unserer einzigartigen Google optimierten e-Paper Software.
Programming<br />
7. Engineering Units - Up to a five character engineering<br />
units message may be assigned for<br />
Conditional points.<br />
a. Programming Engineering Units - Use the<br />
UP (↑) or DOWN (↓) Arrow Keys to select "Eng<br />
units" and press ENTER. The display reads<br />
"units�XXXXX�".<br />
b. Use the Alphanumeric keypad to enter the<br />
desired Engineering Units message. When the<br />
desired message is displayed, press ENTER<br />
and the display returns to the "Eng units" menu<br />
item in the Point Setup Menu.<br />
8. Alarms - Up to five alarms can be programmed<br />
for each Conditional Point. These alarms can be<br />
any combination of None, Abnormal, True, or<br />
False alarm types.<br />
4-40<br />
a. Programming Alarms - Use the UP (↑) or<br />
DOWN (↓) Arrow Keys to highlight "Alarms" and<br />
press ENTER. The display reads either "Alm<br />
limits" or "Alm delay”.<br />
b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight "Alm limits” and press ENTER. The<br />
display reads "alarm #? x".<br />
c. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the desired Alarm Number, up to five<br />
possible, and press ENTER. The display will<br />
read one of the Alarm Types.<br />
NOTE<br />
High, Low, Rate. Open, and Close Alarm<br />
Types are not available for Conditional Point<br />
Types. If any of these Alarm Types are chosen,<br />
the display will read "ILLOGICAL".<br />
d. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the type desired. If "Type=none'“ is chosen,<br />
press ENTER and the display returns to<br />
"Alm limits". If "Type=abnorm", "Type=true", or<br />
"Type=false" is chosen, press ENTER and the<br />
display reads "contact #? X” .<br />
e. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the Contact Number desired and press<br />
ENTER.<br />
f. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight "Alm delay" and press ENTER. The<br />
display reads "seconds�XX�".<br />
g. Use the Numeric keypad to enter the desired<br />
Alarm Delay and press ENTER.<br />
4.6.13 External Point Types. External<br />
Point Types use data sent via the Com port to the<br />
<strong>Recorder</strong> for trending or other uses.<br />
A. Programming Parameters - External<br />
Point type programming requires setting parameters<br />
for:<br />
• Point Tag (up to 10 characters)<br />
• Input Scale<br />
• Output Scale<br />
• Timeout<br />
• Engineering Units (up to five characters)<br />
• Alarm Setpoints (Limits, Deadband and<br />
Delay)<br />
• Chart Scale<br />
Each of these parameters is discussed in detail in<br />
the following paragraphs.<br />
1. At the “COMMAND” prompt display, press the<br />
PROGram Key.<br />
2. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll to “Points” and press ENTER.<br />
3. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll to “Prog point” and press ENTER to begin<br />
programming a point.<br />
4. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll to the Point to be programmed, 1 to 9 or A<br />
to C and press ENTER.<br />
5. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll to the desired point option and press<br />
ENTER.<br />
6. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll to “External” and press ENTER.<br />
7. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
scroll through the menu items in the Point Setup<br />
Menu until “Point tag” appears and press ENTER.<br />
B. Point Tag - A Point Tag (name) can be<br />
established for each point programmed. This tag<br />
can be up to ten characters long.<br />
1. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the digit and the Left (�) or Right (�) Arrow<br />
Keys to move to a position to program the desired<br />
Point Tag and press ENTER.<br />
Siemens AG C79000-G7374-C211-01<br />
<strong>SIREC</strong> D Manual