Programming<br />

7. Engineering Units - Up to a five character engineering<br />

units message may be assigned for<br />

Conditional points.<br />

a. Programming Engineering Units - Use the<br />

UP (↑) or DOWN (↓) Arrow Keys to select "Eng<br />

units" and press ENTER. The display reads<br />

"units�XXXXX�".<br />

b. Use the Alphanumeric keypad to enter the<br />

desired Engineering Units message. When the<br />

desired message is displayed, press ENTER<br />

and the display returns to the "Eng units" menu<br />

item in the Point Setup Menu.<br />

8. Alarms - Up to five alarms can be programmed<br />

for each Conditional Point. These alarms can be<br />

any combination of None, Abnormal, True, or<br />

False alarm types.<br />

4-40<br />

a. Programming Alarms - Use the UP (↑) or<br />

DOWN (↓) Arrow Keys to highlight "Alarms" and<br />

press ENTER. The display reads either "Alm<br />

limits" or "Alm delay”.<br />

b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

highlight "Alm limits” and press ENTER. The<br />

display reads "alarm #? x".<br />

c. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

select the desired Alarm Number, up to five<br />

possible, and press ENTER. The display will<br />

read one of the Alarm Types.<br />

NOTE<br />

High, Low, Rate. Open, and Close Alarm<br />

Types are not available for Conditional Point<br />

Types. If any of these Alarm Types are chosen,<br />

the display will read "ILLOGICAL".<br />

d. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

select the type desired. If "Type=none'“ is chosen,<br />

press ENTER and the display returns to<br />

"Alm limits". If "Type=abnorm", "Type=true", or<br />

"Type=false" is chosen, press ENTER and the<br />

display reads "contact #? X” .<br />

e. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

select the Contact Number desired and press<br />

ENTER.<br />

f. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

highlight "Alm delay" and press ENTER. The<br />

display reads "seconds�XX�".<br />

g. Use the Numeric keypad to enter the desired<br />

Alarm Delay and press ENTER.<br />

4.6.13 External Point Types. External<br />

Point Types use data sent via the Com port to the<br />

<strong>Recorder</strong> for trending or other uses.<br />

A. Programming Parameters - External<br />

Point type programming requires setting parameters<br />

for:<br />

• Point Tag (up to 10 characters)<br />

• Input Scale<br />

• Output Scale<br />

• Timeout<br />

• Engineering Units (up to five characters)<br />

• Alarm Setpoints (Limits, Deadband and<br />

Delay)<br />

• Chart Scale<br />

Each of these parameters is discussed in detail in<br />

the following paragraphs.<br />

1. At the “COMMAND” prompt display, press the<br />

PROGram Key.<br />

2. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll to “Points” and press ENTER.<br />

3. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll to “Prog point” and press ENTER to begin<br />

programming a point.<br />

4. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll to the Point to be programmed, 1 to 9 or A<br />

to C and press ENTER.<br />

5. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll to the desired point option and press<br />

ENTER.<br />

6. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll to “External” and press ENTER.<br />

7. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

scroll through the menu items in the Point Setup<br />

Menu until “Point tag” appears and press ENTER.<br />

B. Point Tag - A Point Tag (name) can be<br />

established for each point programmed. This tag<br />

can be up to ten characters long.<br />

1. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

select the digit and the Left (�) or Right (�) Arrow<br />

Keys to move to a position to program the desired<br />

Point Tag and press ENTER.<br />

Siemens AG C79000-G7374-C211-01<br />

<strong>SIREC</strong> D Manual