4. Reset print - The program in the <strong>Recorder</strong> allows<br />
point reset data to be logged on the<br />
Alarm/Event Data Log, at the time of the reset, or<br />
if enabled, be stored to disk (4.7.2). This option<br />
can be toggled ON or OFF for each resettable<br />
point.<br />
a. Programming Reset Print - From the Reset<br />
Control Setup Menu, use the UP (↑) DOWN (↓)<br />
Arrow Keys to highlight "Reset print" and press<br />
ENTER. The display will read either "print=YES"<br />
or "print=NO".<br />
b. Use the YES or NO Key to select either<br />
"print=YES" "print=NO" and press ENTER. The<br />
display will return to "Reset print' in the Reset<br />
Control Setup Menu.<br />
5. Auto Reset - When programming High Peak,<br />
Low Peak, Totalize, Time Average, and Gated<br />
Timer points, the system allows an Auto Reset<br />
function. If Auto Reset is set up, the point being<br />
programmed will reset at programmed intervals,<br />
from once a minute to once a month. The system<br />
will prompt for the Start Time and Interval for<br />
which that point will reset.<br />
NOTE<br />
If Auto Reset is disabled, resettable points<br />
may only be reset manually.<br />
NOTE<br />
Time Average, High Peak, and Low Peak<br />
points reset to the current value of the base<br />
point. Totalize points reset to zero.<br />
a. Selecting Auto Reset - From the Reset<br />
Control Setup Menu, use the UP (↑) or DOWN<br />
(↓) Arrow Keys to highlight "Auto reset" in the<br />
Reset Control Setup Menu and press ENTER.<br />
The display will read either "Auto off", "Daily",<br />
"Weekly", or "Monthly".<br />
b. Selecting Auto Off - Use the UP (↑) or<br />
DOWN (↓) Arrow Keys to highlight "Auto off"<br />
and press ENTER. The display will return to<br />
"Auto reset" in the Reset Control Setup Menu.<br />
Automatic reset of the programmed point is now<br />
disabled.<br />
Siemens AG C79000-G7374-C211-01<br />
<strong>SIREC</strong> D Manual<br />
Programming<br />
c. Daily Auto Reset - Use the UP (↑) DOWN<br />
(↓) Arrow Keys to highlight "Daily" and press<br />
ENTER. The display will read "start XX:XX". The<br />
Start Time is entered in a 24-hour clock format<br />
in Hours (00 through 23) and Minutes (00<br />
through 59). This is the time the first reset will<br />
begin, after this the point will reset at the “interval”<br />
rate. (see below).<br />
d. Setting Up Start Time - If the Start Time is<br />
correct, press ENTER and proceed to Interval. If<br />
the Start Time is not correct, press NO and the<br />
display reads "str hrs �XX�”. (for STaRt<br />
hours). Use the Numeric Keypad to enter the<br />
desired Start Hours. Up to 23 hours may be<br />
programmed. When the correct Start Hours are<br />
displayed press ENTER and the display reads<br />
"str mins �XX�". Use the Numeric keypad to<br />
enter the desired Start Minutes. Up to 59 minutes<br />
may be programmed. When the correct<br />
Start Minutes are displayed, press ENTER and<br />
the display returns to "start XX:XX". If the Start<br />
Time displayed is correct, press ENTER and the<br />
display reads "intrvl XX:XX”.<br />
e. Setting Up Interval Time - It the displayed<br />
Interval Time is correct, press ENTER and the<br />
display returns to "Auto reset" in the Reset<br />
Control Setup Menu. If the Interval Time is not<br />
correct, press NO and the display reads "int<br />
hrs�XX�". Use the Numeric keypad to enter<br />
the desired Interval Hours. Up to 23 hours may<br />
be programmed. When the correct Interval<br />
Hours are displayed press ENTER and the display<br />
reads "int mins�XX�". Use the Numeric<br />
keypad to enter the desired Interval Minutes. Up<br />
to 59 minutes may be programmed. When the<br />
correct Interval Minutes are displayed, press<br />
ENTER and the display returns to "intrvl<br />
XX:XX". If the Interval Time displayed is correct,<br />
press ENTER and the display returns to the<br />
"Auto reset" prompt in the Reset Control Setup<br />
Menu.<br />
f. Interval Programming for Totalize Point<br />
Types - When programming a Totalization<br />
Point, the Interval represents the frequency of<br />
which the Totalization value will be reset to zero.<br />
The Totalization value will be logged on the<br />
Alarm/Event Data Log before the value is reset<br />
if the reset print is enabled. The interval time is<br />
entered in a 24-hour clock format in Hours (00<br />
through 24) and Minutes (00 through 59). The<br />
longest time interval that can be entered is<br />
24:00 which represents a reset interval of once<br />
every 24 hours.<br />