Programming<br />
4-32<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Decimal fix” and press ENTER.<br />
b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight the desired number of decimal places<br />
required and press ENTER.<br />
4. Programming Basepoint - A Basepoint must<br />
be established to perform the Moving Average<br />
calculations on.<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Basepoint” and press ENTER.<br />
b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight the desired point to be the basepoint<br />
and press ENTER.<br />
5. Programming Time Period - The Time Period<br />
is the time base used to set the duration (time) of<br />
the moving window. The point does not become<br />
valid until this time has elapsed.<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight "Time period" and press ENTER. The<br />
display reads "minutes�XXXX�”.<br />
b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the digit and the LEFT (�) or RIGHT (�)<br />
Arrow Keys to move to a position to enter the<br />
desired Time Period. A maximum 1440 minutes<br />
(24 hours) may be entered. When the desired<br />
Time Period is displayed, press ENTER and the<br />
display returns to "Time Period".<br />
6. Programming Engineering Units - Up to a<br />
five character engineering units message may be<br />
assigned for Calculated points.<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Eng units” and press ENTER.<br />
b. Use the Alphanumeric keypad to enter the<br />
desired Engineering Units message and press<br />
ENTER.<br />
7. Alarms - Refer to Alarms Setup in Paragraph<br />
4.6.14 below for instructions on programming<br />
alarms.<br />
8. Assigning a Point to a Chart Scale - Each<br />
point must be assigned to a Chart Scale.<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Chart scale” and press ENTER.<br />
b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
select the Chart Scale numeral and press<br />
ENTER. To leave the programming menu, press<br />
EXIT until the “Command” prompt is displayed.<br />
G. Gated Timer - The Gated Timer function<br />
allows a timer, measuring in seconds, to be<br />
controlled by a ‘gate’ from a logic point. For<br />
example, if a point is measuring temperature and<br />
you wanted to know the total amount of time the<br />
temperature measured by this point is above or<br />
below a certain level, a Conditional Point can be<br />
programmed to be ‘true' only when the temperature<br />
is above or below a set level. A Gated Timer Point<br />
can then be programmed to be turned ON only<br />
when the Conditional Point is in the true state. The<br />
Gated Timer Point will then only be timing when the<br />
temperature is above or below a set level. The timer<br />
will continue to accumulate time, in seconds, each<br />
time it is turned on. The Gated Timer Point can be<br />
reset at programmable time intervals and alarms<br />
can be set to alarm if the timer total goes above a<br />
programmed time interval in seconds.<br />
1. Programming Parameters - The following<br />
steps detail programming from the Main Menu:<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Prog point” and press ENTER.<br />
b. Use the numeric keypad to enter the point to<br />
be programmed, 1 to 9 or A to C and press<br />
ENTER.<br />
c. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight the desired point option and press<br />
ENTER.<br />
d. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Calculated” and press ENTER.<br />
e. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Gated timer” and press ENTER.<br />
2. Programming Point Tag - Up to a ten character<br />
alphanumeric label can be assigned to each<br />
point.<br />
a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />
highlight “Point tag” and press ENTER.<br />
b. Use the alphanumeric keypad to enter the<br />
desired Point Tag and press ENTER.<br />
Siemens AG C79000-G7374-C211-01<br />
<strong>SIREC</strong> D Manual