01.01.2013 Aufrufe

SIREC D Display Recorder 7ND4000

SIREC D Display Recorder 7ND4000

SIREC D Display Recorder 7ND4000

MEHR ANZEIGEN
WENIGER ANZEIGEN

Erfolgreiche ePaper selbst erstellen

Machen Sie aus Ihren PDF Publikationen ein blätterbares Flipbook mit unserer einzigartigen Google optimierten e-Paper Software.

3. Trigger - Selecting Trigger will arm the unit to<br />

record when an external or internal event takes<br />

place. Internal Record-On-Alarm Triggers are set<br />

in the Record Setup menu while External Event<br />

Triggers are set in the Digital Input/Output Setup<br />

menu under the PROGram Button. If the <strong>Recorder</strong><br />

is set in the record TRIGGER mode, either<br />

of these event triggers will control the Record<br />

ON or Record OFF function depending on<br />

whether the events are active or inactive. To set<br />

the Record Mode to Trigger, perform the following<br />

steps and refer to Figure 3-32:<br />

1 0 3 7 2 2 M A<br />

a. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

highlight “Record On/Off” and press ENTER.<br />

b. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

highlight “Trigger” and then press ENTER.<br />

c. A pop up window will ask to confirm the selection<br />

“trigger on?”. Press “YES” to accept the<br />

Trigger ON state or “No” to exit without turning<br />

the trigger mode ON.<br />

VIEW BR OW S 04/16/97 4:59:29 JOG MENU<br />

ENTER<br />

ENTER<br />

ENTER<br />

ENTER<br />

trigger on?<br />

DISP 04/16/97 PROG 4:59:29 FUNC EXIT<br />

04/16/97 4:59:29 EXIT<br />

04/16/97 4:59:29 EXIT<br />

YES NO EXIT<br />

04/16/97 4:59:29 EXIT<br />

Figure 3-32 Turn Trigger Mode to ON Flow<br />

Chart<br />

NOTE<br />

Triggered recordings can only be made if<br />

the disk record mode is set to Fill-To-End.<br />

See Chapter 4. Cyclic files cannot be triggered.<br />

Siemens AG C79000-G7374-C211-01<br />

<strong>SIREC</strong> D Manual<br />

NOTE<br />

Operation<br />

Trigger Mode can be invoked with the <strong>Recorder</strong><br />

in the Record ON or OFF Mode.<br />

With the Trigger Mode turned ON, the current<br />

record status is shown in the Disk Info<br />

Window in the top right corner of the<br />

screen. If the unit is not recording, this window<br />

will show REC TRIG. To start recording,<br />

without waiting for a trigger, turn Record<br />

ON as detailed in paragraph 3.4.4.A.2.<br />

B. Activate Point - This menu item returns a<br />

temporarily bypassed point or points to the<br />

measurement cycle for measuring inputs and<br />

displaying information. To activate a point perform<br />

the following steps and use the flow chart shown in<br />

Figure 3-33:<br />

1. Press the FUNC Key on the Main Menu Bar.<br />

2. Use the UP (↑) or DOWN (↓) Arrow Keys to<br />

highlight “Activate pt” and press ENTER.<br />

3. Use the pup-up numeric keypad to enter the<br />

point number to activate and press ENTER on<br />

the Menu Bar.<br />

4. The display then scrolls to the next point.<br />

When point activation is finished, press EXIT in<br />

the pop-up keypad and the display will return to<br />

the “Activate pt” display.<br />

103723MA<br />

VIEW BROW S 04/16/97 4:59:29 JOG MENU<br />

ENTER<br />

ENTER<br />

DISP 04/16/97 PR4:59:29 OG FUNC EXIT<br />

04/16/97 4:59:29 EXIT<br />

A<br />

B<br />

C<br />

P oint? 1<br />

7 8 9<br />

4 5 6<br />

3 2 1<br />

04/16/97 4:59:29 EXIT EXIT<br />

Figure 3-33 Activate Point Flow Chart<br />

3-17