4.6.2 Constants. This menu item is available<br />
through the Program Menu and allows the user to<br />
program up to twelve different constants for use in<br />
equations for point programming. These constants,<br />
referred to as Kx (where x = 1 to 9, A,B, and C), are<br />
substituted into equations instead of writing the<br />
constant value. This saves on characters when<br />
programming an equation.<br />
A. Programming Constants - The following<br />
steps and Figure 4-10 guide the user in programming<br />
Constants:<br />
1. Press the Menu Button on the <strong>Display</strong> Button<br />
Bar. The Command Menu Bar will be displayed.<br />
2. Press the PROGram Button on the Command<br />
Button Bar. The Program Menu box will be displayed.<br />
3. Use the Up (↑) or Down (↓) Arrow Keys, on the<br />
Button Bar, to scroll to “Points” and press the<br />
ENTER Button. The Points/Constants Menu box<br />
will display.<br />
4.Use the Up (↑) or Down (↓) Arrow Keys, on the<br />
Button Bar, to scroll to “Constants” and press the<br />
ENTER Button. The Constant Selection box will<br />
be displayed.<br />
5.Use the Up (↑) or Down (↓) Arrow Keys, on the<br />
Button Bar, to scroll to “Define KX” (where X is the<br />
constant number you wish to program) and press<br />
the ENTER Button. A Pop-Up Window for defining<br />
a Constant will appear.<br />
6. Use the Numeric Keypad to program the constant<br />
value desired (thirteen digits possible including<br />
decimal places).<br />
7. After the Constant has been programmed,<br />
press ENTER. The display will return to the “Define<br />
KX” menu.<br />
8. Use Steps 5, 6, and 7 to program as many<br />
Constants as needed (12 max.). When you are<br />
through programming Constants, press EXIT as<br />
needed to get back to the <strong>Display</strong> screen.<br />
Siemens AG C79000-G7374-C211-01<br />
<strong>SIREC</strong> D Manual<br />
103735M A<br />
04/16/97 4:59:29<br />
Programming<br />
Figure 4-10 Program Constants Flow Chart<br />
4.6.3 Program point. This menu item is<br />
available through the Program Menu that allows the<br />
user to setup, copy, restore, modify, or delete a<br />
point's parameters. The programming sequence<br />
follows a general order for custom programming and<br />
the system prompts you to submit various parameters.<br />
Refer to Figure 4-11, Points Setup Flow Chart.<br />
A. Point Number - When you select the Program<br />
Point menu item from the Program Menu, the<br />
system prompts for point number, "point? X". Up to<br />
twelve points can be entered in the database and<br />
any number from 1 to 9 or A to C can be selected as<br />
the point number.<br />
NOTE<br />
Points 1 to 12 may be any point type and<br />
any or all of these points can be direct inputs.<br />
Points 7 to 9 and A to C can also be<br />
Calculated, Conditional, or External point<br />
types.<br />
ENTER<br />