1. Copper Tube – 2” and smaller: Soldered ends, except in heating hot water and<br />

low pressure steam service, where threaded ends shall be used.<br />

2. Steel Pipe – 2” and smaller: Threaded or grooved-end.<br />

3. Steel Pipe – 2-1/2” and larger: Flanged or grooved-end.<br />

4. At all piping hot taps, provide a gate valve at the hot tap and a butterfly valve for<br />

shut-off service. Hot taps shall be provided only where approved by the Engineer.<br />

3.03 VALVE INSTALLATIONS:<br />

Valve Application Table<br />

SERVICE VALVE TYPE<br />

Plumbing Water Services – 2” and Ball Valve<br />

smaller<br />

Plumbing Water Services – 2-1/2” Butterfly Valve<br />

and larger<br />

Plumbing Pressure Reducing Bypass – Ball Valve<br />

2” and smaller<br />

Plumbing Pressure Reducing Bypass – Butterfly Valve<br />

2-1/2” and larger<br />

Plumbing Balancing – 2” and Calibrated Balancing Valve<br />

smaller<br />

Plumbing Balancing – 2-1/2” Eccentric Plug Balancing Valve<br />

and larger<br />

Plumbing Check Valves – 2” Swing Check<br />

and smaller<br />

Plumbing Pump Discharge Non-Slam Swing Check<br />

Check Valve – all sizes<br />

Sewage Ejector and/or Sump Pump Swing Check<br />

Discharge Check Valve – all sizes<br />

Condensate Piping Shut-off – 2” Ball Valve<br />

and smaller<br />

A. Locate valves for easy access, and provide separate support where necessary.<br />

B. Install valves and unions for each fixture and item of equipment in a manner to allow<br />

equipment removal without system shut-down. Unions are not required on flanged<br />

devices.<br />

C. Install 3-valve bypass around each pressure-reducing valve using throttling type valves.<br />

D. Gate and globe valves shall be installed with the stem in the upright position. In overhead<br />

horizontal piping, ball valves shall be installed with the handle at the side or bottom of the<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

220523 - 7 GENERAL-DUTY VALVES FOR<br />

PLUMBING PIPING