2.04 STARTERS:<br />

A. Furnish individual combination type full NEMA rated starters with HMCP or fused<br />

disconnect switch for all motors provided (except for starters that are shown to be provided<br />

in motor control centers). All combination starters shall be adequately braced for the fault<br />

current available. 42,000 AIC @ 480V, three phase and 65,000 AIC @ 208V, threephase<br />

shall be the minimum ratings.<br />

1. Enclosures: NEMA Type 1, general purpose enclosures with padlock ears, except<br />

in wet locations, where NEMA Type 3R enclosures with conduit hubs shall be used.<br />

Units in hazardous locations shall have enclosure of proper NEC class and<br />

division appropriate for the application.<br />

2. All starters for three-phase motors shall be of magnetic type, complete with the<br />

following accessories:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Three-leg Class 10 trip-free overload protection with externally operated<br />

manual reset and visual trip indicator.<br />

b. Separate three-phase voltage monitor to provide quick-trip on single<br />

phasing or phase reversal, with automatic reset.<br />

c. Control transformers with fused primary and secondary.<br />

d. 120-volt holding coils.<br />

e. Integral Hand-Off-Auto switch for single-speed motors.<br />

f. Integral High-Low-Off-Auto switch for two-speed motors.<br />

g. High-to-low speed time delay relay for two-speed starters.<br />

h. Auxiliary contacts, one N.O. and one N.C. minimum.<br />

i. “Run” pilot light.<br />

3. Two-speed, two-winding starters shall incorporate both mechanical and electrical<br />

interlocks between the high and low speed contactors and shall have individual<br />

overload current protection and auxiliary contacts for each speed.<br />

4. Starters for single-phase motors shall have horsepower rated thermal overload<br />

switches.<br />

5. All starters shall be full NEMA rated. IEC rated and/or NEMA equivalent rated<br />

starters are not acceptable. All starters shall be listed and labeled by NEMA, UL,<br />

and CSA.<br />

6. Provide complete submittal data for all single and three-phase starters.<br />

7. Approved manufacturers are Allen-Bradley, Cutler-Hammer, General Electric,<br />

Square D, and S & S.<br />

B. Furnish all necessary control devices such as speed controls, transformers, and relays as<br />

required for proper operation for all equipment furnished under this Division.<br />

C. Furnish all remote switches and/or push-button stations required for manually operated<br />

equipment, complete with low energy pilot lights of an approved type.<br />

D. Motors, starters, and other electrical control equipment installed in moist areas or in areas<br />

of special conditions, such as areas where explosive gases are present, shall be designed<br />

and approved for installation in such areas.<br />

E. Furnish circuit and purpose identification for each remote manual switch and/or pushbutton<br />

station furnished herein. Identification may be by means of either an engraved<br />

plastic sign for permanent mounting to wall below switch or a stamping on switch cover<br />

plate. All such identification signs and/or switch covers in finished areas shall match other<br />

hardware in the immediate areas.<br />

23 0513 - 6 MECHANICAL/ELECTRICAL REQ.<br />

FOR MECHANICAL EQUIPMENT