J. Prime-Coat Finish: Manufacturer's standard prime-coat finish ready for field painting.<br />

K. Galvanized Finish: After fabrication, hot-dip galvanize complying with ASTM A 123/A 123M.<br />

L. Factory-Painted Finish: Comply with NAAMM's "Metal Finishes Manual for Architectural and<br />

Metal Products" for recommendations for applying and designating finishes.<br />

1. Surface Preparation: Clean surfaces to comply with SSPC-SP 1, "Solvent Cleaning," to<br />

remove dirt, oil, grease, and other contaminants that could impair paint bond. Grind<br />

welds and polish surfaces to a smooth, even finish. Remove mill scale and rust, if present,<br />

from uncoated steel, complying with SSPC-SP 5/NACE No. 1, "White Metal Blast<br />

Cleaning," or with SSPC-SP 8, "Pickling."<br />

2. Interior Surfaces of Pole: One coat of bituminous paint, or otherwise treat for equal<br />

corrosion protection.<br />

3. Exterior Surfaces: Manufacturer's standard finish consisting of one or more coats of primer<br />

and two finish coats of high-gloss, high-build polyurethane enamel.<br />

2.9 ALUMINUM POLES<br />

a. Color: As selected by Architect or Interior Designer from manufacturer's full range.<br />

A. Poles: Seamless, extruded structural tube complying with ASTM B 429/B 429M, Alloy 6063-T6<br />

with access handhole in pole wall.<br />

B. Poles: ASTM B 209, 5052-H34 marine sheet alloy with access handhole in pole wall.<br />

1. Shape: as noted on drawings.<br />

2. Mounting Provisions: Butt flange for bolted mounting on foundation or breakaway<br />

support.<br />

C. Pole-Top Tenons: Fabricated to support luminaire or luminaires and brackets indicated, and<br />

securely fastened to pole top.<br />

D. Grounding and Bonding Lugs: Welded 1/2-inch threaded lug, complying with requirements in<br />

Section 26 0526 "Grounding and Bonding for Electrical Systems," listed for attaching grounding<br />

and bonding conductors of type and size listed in that Section, and accessible through handhole.<br />

E. Brackets for Luminaires: Detachable, with pole and adapter fittings of cast aluminum. Adapter<br />

fitting welded to pole and bracket, then bolted together with stainless-steel bolts.<br />

1. Tapered oval cross section, with straight tubular end section to accommodate luminaire.<br />

2. Finish: Same as pole.<br />

F. Prime-Coat Finish: Manufacturer's standard prime-coat finish ready for field painting.<br />

G. Aluminum Finish: Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal<br />

Products" for recommendations for applying and designating finishes.<br />

1. Finish designations prefixed by AA comply with the system established by the Aluminum<br />

Association for designating aluminum finishes.<br />

2. Natural Satin Finish: Provide fine, directional, medium satin polish (AA-M32); buff<br />

complying with AA-M20; and seal aluminum surfaces with clear, hard-coat wax.<br />

Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/19/2012<br />

265600 - 9 EXTERIOR LIGHTING