PART 1 – GENERAL<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 22 0548<br />

VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND EQUIPMENT<br />

1.01 DESCRIPTION OF WORK:<br />

A. Extent of vibration control work required by this Section is indicated on drawings and<br />

schedules, and/or specified in other Division 22 sections.<br />

1. All plumbing equipment and piping as noted or in the specification shall be<br />

mounted on vibration isolators to prevent the transmission of vibration and<br />

mechanically transmitted sound to the building structure. Vibration isolators shall<br />

be selected in accordance with the weight distribution so as to produce reasonably<br />

uniform deflection.<br />

2. All such systems must be installed in strict accordance with component<br />

manufacturer’s and building construction standards. Whenever a conflict occurs<br />

between the manufacturer's or construction standards, the most stringent shall<br />

apply.<br />

3. Any variance from or non-compliance with these specification requirements shall<br />

be corrected by the contractor in an approved manner.<br />

B. The work of this Section includes, but is not limited to, the following:<br />

1. Vibration isolation for all plumbing systems/equipment, including, but not limited<br />

to, the following: Pumps (all types)<br />

2. Vibration isolation for piping.<br />

3. Equipment isolation bases.<br />

4. Flexible piping connections.<br />

C. Vibration control products furnished as an integral part of factory-fabricated equipment<br />

shall be accepted only if they fully comply with the requirements of this Section.<br />

D. For additional and supplemental requirements, refer to other Division 22 sections for<br />

equipment foundations; hangers; sealants; gaskets; requirements of electrical connections<br />

to equipment isolated on vibration control products;<br />

1.02 QUALITY ASSURANCE:<br />

A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of vibration<br />

control products, of types, sizes, and capacities required, whose products have been in<br />

satisfactory use in similar service for not less than five years.<br />

1.03 SUBMITTALS:<br />

1. Except as otherwise indicated, vibration control products shall be obtained from a<br />

single manufacturer and shall be certified by the manufacturer.<br />

2. Engage manufacturer to provide technical supervision of installation of support<br />

isolation and associated inertia bases.<br />

22 0548 - 1 VIBRATION AND SEISMIC<br />

CONTROLS FOR PLUMBING<br />

PIPING AND EQUIPMENT