Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 23 0548<br />

VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT<br />

PART 1 – GENERAL<br />

1.01 DESCRIPTION OF WORK:<br />

A. Extent of vibration control work required by this Section is indicated on drawings<br />

and schedules, and/or specified in other Division 23 sections.<br />

1. All mechanical equipment, piping and ductwork as noted or in the<br />

specification shall be mounted on vibration isolators to prevent the<br />

transmission of vibration and mechanically transmitted sound to the<br />

building structure. Vibration isolators shall be selected in accordance with<br />

the weight distribution so as to produce reasonably uniform deflection.<br />

2. All such systems must be installed in strict accordance with component<br />

manufacturer’s and building construction standards. Whenever a conflict<br />

occurs between the manufacturer's or construction standards, the most<br />

stringent shall apply.<br />

3. Any variance from or non-compliance with these specification<br />

requirements shall be corrected by the contractor in an approved manner.<br />

B. The work of this Section includes, but is not limited to, the following:<br />

1. Vibration isolation for all mechanical systems/equipment, including, but<br />

not limited to, the following:<br />

AC Units<br />

Air Handling Units<br />

Chillers<br />

Compressors<br />

Computer Room Units<br />

Condensers<br />

Condensing Units<br />

Cooling Towers<br />

2. Vibration isolation for piping and ductwork.<br />

3. Equipment isolation bases.<br />

4. Flexible piping connections.<br />

Fan-Powered Boxes<br />

Fans (all types, including life<br />

safety fans)<br />

Pumps (all types)<br />

Rooftop HVAC Units<br />

Unit Heaters<br />

Heat Pum<br />

C. Vibration control products furnished as an integral part of factory-fabricated equipment<br />

shall be accepted only if they fully comply with the requirements of this Section.<br />

D. For additional and supplemental requirements, refer to other Division 23 sections for<br />

equipment foundations; hangers; sealants; gaskets; requirements of electrical connections<br />

to equipment isolated on vibration control products; and requirements of duct connections<br />

to air handling equipment isolated on vibration control products.<br />

1.02 QUALITY ASSURANCE:<br />

23 0548 - 1 VIBRATION AND SEISMIC<br />

CONTROLS FOR HVAC PIPING<br />

AND EQUIPMENT