PART 1 – GENERAL<br />

1.01 DESCRIPTION OF WORK:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 221123<br />

PLUMBING PUMPS<br />

A. Plumbing pump types and capacities are as indicated on the drawings and schedules, and<br />

by requirements of this Section.<br />

B. Types of pumps specified in this Section include the following:<br />

1. In-Line Circulation Pumps.<br />

2. Water Pressure Booster Systems.<br />

3. Pedestal Type Sump Pumps.<br />

4. Submersible Sump Pumps.<br />

C. Pumps furnished as part of factory-fabricated equipment are specified as part of<br />

equipment assembly in other Division 22 sections.<br />

D. Refer to other Division 22 sections for insulation of pump housings and vibration control of<br />

plumbing pumps.<br />

E. Provide the following electrical work as work of this Section, complying with requirements<br />

of Division 26 sections:<br />

1.02 QUALITY ASSURANCE:<br />

1. Control wiring between field-installed controls, indicating devices, and pump<br />

control panels.<br />

A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of plumbing<br />

pumps with characteristics, sizes, and capacities required, whose products have been in<br />

satisfactory use in similar service for not less than 5 years.<br />

B. Codes and Standards:<br />

1. HI Compliance: Design, manufacture, and installation of plumbing pumps shall<br />

be in accordance with HI (Hydraulic Institute) standards.<br />

2. UL Compliance: Design, manufacture, and installation of plumbing pumps shall<br />

be in accordance with UL 778, "Motor Operated Water Pumps."<br />

3. UL and NEMA Compliance: Provide pumps with electric motors and components<br />

which are listed and labeled by Underwriters Laboratories and comply with NEMA<br />

standards.<br />

4. SSPMA Compliance: Testing and rating of sump and sewage pumps shall be in<br />

accordance with Sump and Sewage Pump Manufacturers Association (SSPMA)<br />

standards. Pumps shall be provided with certified rating seal.<br />

5. National Electrical Code (NEC).<br />

6. American Society for Testing and Materials (ASTM).<br />

221123 - 1 PLUMBING PUMPS